Indicates immediate danger.
If not avoided, death or serious injury will result.
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.
Indicates a risk of flawed results and possible damage to the equipment.
Indicates immediate danger.
If not avoided, death or serious injury will result.
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.
Indicates a risk of flawed results and possible damage to the equipment.
Indicates immediate danger.
If not avoided, death or serious injury will result.
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.
Indicates a risk of flawed results and possible damage to the equipment.
The Operating Instructions must always be at hand wherever the device is being used. In addition to the Operating Instructions, attention must also be paid to any generally applicable and local regulations regarding accident prevention and environmental protection.
All safety and danger notices on the device:The terminals can reach high temperatures.
Only operate the device when all protection devices are fully functional. If the protection devices are not fully functional, there is a danger of:Any safety devices that are not fully functional must be repaired by an authorised specialist before the device is switched on.
Never bypass or disable protection devices.
For the location of the safety and danger notices on the device, refer to the section headed "General remarks" in the Operating Instructions for the device.
Any equipment malfunctions which might impair safety must be remedied before the device is turned on.
This is for your personal safety!
Operation or storage of the device outside the stipulated area will be deemed as not in accordance with the intended purpose. The manufacturer accepts no liability for any damage resulting from improper use.
The servicing information contained in these operating instructions is intended only for the use of qualified service engineers. An electric shock can be fatal. Do not carry out any actions other than those described in the documentation. This also applies to qualified personnel.
All cables and leads must be secured, undamaged, insulated and adequately dimensioned. Loose connections, scorched, damaged or inadequately dimensioned cables and leads must be immediately repaired by authorised personnel.
Maintenance and repair work must only be carried out by an authorised specialist.
It is impossible to guarantee that bought-in parts are designed and manufactured to meet the demands made on them, or that they satisfy safety requirements. Use only original spare parts (also applies to standard parts).
Do not carry out any alterations, installations, or modifications to the device without first obtaining the manufacturer's permission.
Components that are not in perfect condition must be changed immediately.
Copyright of these operating instructions remains with the manufacturer.
Text and illustrations were accurate at the time of printing, subject to change.
We are grateful for suggestions for improvement and information regarding any discrepancies in the operating instructions.
The Fronius Smart Meter IP is a bidirectional electricity meter which optimises self-consumption and records a household's load curve. In conjunction with a Fronius inverter or Fronius Datamanager 2.0 and a Fronius data interface, the Fronius Smart Meter IP provides an overview of a user's own power consumption.
The meter measures the energy flow to the loads or to the public grid and forwards the information via the Modbus RTU/RS485- or TCP interface (LAN/WLAN) to the Fronius inverter or the Fronius Datamanager 2.0.
The Fronius Smart Meter IP is a bidirectional electricity meter which optimises self-consumption and records a household's load curve. In conjunction with a Fronius inverter or Fronius Datamanager 2.0 and a Fronius data interface, the Fronius Smart Meter IP provides an overview of a user's own power consumption.
The meter measures the energy flow to the loads or to the public grid and forwards the information via the Modbus RTU/RS485- or TCP interface (LAN/WLAN) to the Fronius inverter or the Fronius Datamanager 2.0.
The Fronius Smart Meter IP is a bidirectional electricity meter which optimises self-consumption and records a household's load curve. In conjunction with a Fronius inverter or Fronius Datamanager 2.0 and a Fronius data interface, the Fronius Smart Meter IP provides an overview of a user's own power consumption.
The meter measures the energy flow to the loads or to the public grid and forwards the information via the Modbus RTU/RS485- or TCP interface (LAN/WLAN) to the Fronius inverter or the Fronius Datamanager 2.0.
Technical data, markings and safety symbols are located on the Fronius Smart Meter IP. These must NOT be removed or painted over. They warn against incorrect operation which can lead to serious injury and damage.
Symbols on the rating plate: | ||
| CE mark – confirms compliance with applicable EU directives and regulations. The product has been tested by a specific notified body. | |
| WEEE mark – waste electrical and electronic equipment must be collected separately and recycled in an environmentally sound manner in accordance with the European Directive and national law. | |
| UKCA mark – confirms compliance with applicable UK directives and regulations. | |
| RCM mark – tested in accordance with the requirements of Australia and New Zealand. |
The Fronius Smart Meter IP is a fixed piece of equipment for public grids of TN/TT systems and may only be used to measure loads and self-consumption.
The Fronius Smart Meter IP is required for systems with a battery storage system and/or a Fronius Ohmpilot installed for communication between the individual components.
The installation is carried out on an indoor DIN rail with corresponding back-up fuses, which are adapted to the cable cross-sections of the copper conductors and to the maximum current of the meter. The Fronius Smart Meter IP must only be operated in accordance with the specifications in the enclosed documentation and in accordance with local laws, regulations, provisions, standards and within the limits of technical possibilities. Any use of the product other than as described in the intended use shall be deemed to be not in accordance with the intended purpose.
The available documentation forms part of the product and must be read, observed and kept in good condition. It must also be accessible at all times at the place of installation. Fronius International GmbH assumes no responsibility for compliance with or non-compliance with these laws or regulations in connection with the installation of the product.
(1) | Fronius Smart Meter IP |
(2) | Quick Start Guide |
The Smart Meter can be installed in the following positions in the system:
Positioning at the feed-in point
Positioning at the consumption point
The Fronius Smart Meter IP has accuracy class 1 when measuring active energy (EN IEC 62053-21) in the voltage ranges 208 - 480 VLL and 100 - 240 VLN. For further details see Technical data on page (→).
The Fronius Smart Meter IP is backup power capable with Modbus RTU/TCP data cabling. When connecting via Modbus TCP, make sure that the grid reset time is increased by starting the network. Fronius recommends a Modbus RTU connection.
(1) | Voltage transformer connection area |
(2) | LAN port |
(3) | DIP switch
|
(4) | Modbus RTU connection area |
(5) | LED indicators |
(6) | WLAN access point and reset function button
|
(7) | QR code to start the Setup wizard |
(8) | AC connection area |
(1) | Voltage transformer connection area |
(2) | LAN port |
(3) | DIP switch
|
(4) | Modbus RTU connection area |
(5) | LED indicators |
(6) | WLAN access point and reset function button
|
(7) | QR code to start the Setup wizard |
(8) | AC connection area |
The LED status indicators show the operating status and data connection of the Fronius Smart Meter IP.
|
|
(3) | Link 1 LED Steady green: Data connection established with the network |
(4) | Link 2 LED Lights up red: No data connection Flashing red: Open WLAN access point |
(5) | WLAN LED Flashing green: WLAN connection is being established Lights up green: WLAN connection is active |
Please note the following criteria when choosing a location for the Smart Meter:
Only install on a solid, non-flammable surface.
When installing the Smart Meter in a switch cabinet or similar enclosure, make sure that it is of the appropriate safety class and that the hot air that develops will be dissipated by forced-air ventilation.
The Smart Meter is suitable for indoor installation. | ||
The Smart Meter must not be installed or used at altitudes above 2000 m. |
Please note the following criteria when choosing a location for the Smart Meter:
Only install on a solid, non-flammable surface.
When installing the Smart Meter in a switch cabinet or similar enclosure, make sure that it is of the appropriate safety class and that the hot air that develops will be dissipated by forced-air ventilation.
The Smart Meter is suitable for indoor installation. | ||
The Smart Meter must not be installed or used at altitudes above 2000 m. |
Please note the following criteria when choosing a location for the Smart Meter:
Only install on a solid, non-flammable surface.
When installing the Smart Meter in a switch cabinet or similar enclosure, make sure that it is of the appropriate safety class and that the hot air that develops will be dissipated by forced-air ventilation.
The Smart Meter is suitable for indoor installation. | ||
The Smart Meter must not be installed or used at altitudes above 2000 m. |
The Fronius Smart Meter IP can be mounted on a 35 mm DIN rail. The housing comprises 3 modules according to DIN 43880.
The Fronius Smart Meter IP is a hard-wired device and requires a disconnecting device (automatic circuit breaker).
The Fronius Smart Meter IP consumes 30 mA, the nominal capacity of the disconnecting devices and the overcurrent protection is determined by the conductor cross-sections, the mains voltage and the required breaking capacity.
Disconnecting device for the mains terminals
The automatic circuit breaker must protect the mains terminals marked L1, L2 and L3. In rare cases, the neutral conductor has a disconnecting device, which must interrupt both neutral and non-earthed cables concurrently.
Danger from live mains voltage inputs
An electric shock can be fatal.
Switch off the power supply before connecting the mains voltage inputs.
Each live conductor must be connected to the AC terminals as shown in the figures below.
It is recommended to use Fronius CT current transformers (item numbers 41,0010,0104 / 41,0010,0105 / 41,0010,0232). To ensure smooth operation of the Fronius Smart Meter IP and accurate measurement results, all connected current transformers must meet these requirements:
Risk of electric shock due to unintentional opening of hinged current transformers
This can result in severe injury and damage to property.
Switch off the current when working on the current transformers.
Attach a plastic cable tie to the current transformer to prevent unintentional opening.
Observe direction information when installing the current transformers
Negative power values occur when the current transformers are connected incorrectly.
Observe the data sheet and the marking on the current transformer (arrow indicates the direction to the load or to the public grid)
Check the correct position of the black and white cable.
Danger from mains voltage
An electric shock can be fatal.
Switch off the power supply before disconnecting live conductors.
Cable length of the current transformers
Cables that are too long can have a negative effect on the measuring accuracy.
If a cable extension is necessary, use a shielded 0.34 to 1.5 mm2 (AWG 22-16) CAT 5 STP (Shielded Twisted Pair) cable rated for 300 V or 600 V (higher than the operating voltage).
Unusual measured values on unused phases
If unusual measured values occur on unused phases, bypass the unused current transformer inputs.
To do so, for each unused current transformer, connect the terminal marked with a white dot to the terminal marked with a black dot using a short cable.
IMPORTANT!
Ensure sufficient WLAN signal strength at the installation site. If the signal strength is low, a WLAN booster must be installed, for example.
The use of a static IP address is recommended.
Connect the data communication connections of the Fronius Smart Meter IP to the Modbus interface of the Fronius inverter using a CAT 5 STP (Shielded Twisted Pair) or higher data cable.
The Fronius Smart Meter IP can also be connected to the network (LAN / WLAN). This allows software updates to be carried out.
Standard Modbus address & TCP port:To avoid interference, the terminating resistor must be used (see chapter Setting the Modbus RTU terminating resistor on page (→)).
If a battery is installed in the system, the BIAS switch must be set (see chapter Setting the Modbus RTU BIAS on page (→)).
Further settings are necessary on the user interface of the inverter and the Fronius Smart Meter IP (see Advanced settings).
IMPORTANT!
A loose wire can disable an entire area of the network. The data communication connections of the Fronius Smart Meter IP are electrically isolated from hazardous voltages.
Inverter in the system | |
Meter - Fronius Smart Meter IP | |
Fronius or third-party device, connection via Modbus TRU | |
Terminating resistor |
The terminating resistor is integrated in the Fronius Smart Meter IP and is set by a switch.
For information on whether the terminating resistor must be set or not, see chapter Terminating resistors on page (→).
Due to interference, it is recommended that terminating resistors are used as illustrated below to ensure proper functioning.
If the Smart Meter is connected to the same Modbus interface (MB0 or MB1) as the battery, the BIAS switch must be set to ON.
It is recommended to activate the Automatic Updates function during commissioning. The Fronius Smart Meter IP checks for available updates daily and automatically installs them between midnight and 6 o'clock. A precise time can be set.
If this function is not activated, software updates can also be searched for and started manually on the user interface of the device.
The software of the Fronius Smart Meter IP is compatible with the following software versions of connected Fronius components:
IMPORTANT! Settings under the "Meter" menu item are only to be made by trained and qualified personnel!
The service password must be entered in order to access the "Meter" menu item.
The meter is selected in the Fronius Smart Meter menu item. The Fronius Datamanager 2.0 automatically identifies the meter type.
A primary meter and several secondary meters can be selected. The primary meter needs to be configured first before a secondary meter can be selected.
The Fronius Smart Meter IP can be connected with Modbus TCP or Modbus RTU.
IMPORTANT! Settings under the "Meter" menu item are only to be made by trained and qualified personnel!
The service password must be entered in order to access the "Meter" menu item.
The meter is selected in the Fronius Smart Meter menu item. The Fronius Datamanager 2.0 automatically identifies the meter type.
A primary meter and several secondary meters can be selected. The primary meter needs to be configured first before a secondary meter can be selected.
The Fronius Smart Meter IP can be connected with Modbus TCP or Modbus RTU.
Access point:
LAN:
The Fronius Smart Meter IP is configured as the primary meter.
The Current general view menu area displays the power of the PV modules, self-consumption, the energy fed into the grid and the battery charge (if available).
The Fronius Smart Meter IP is configured as a secondary meter.
Modbus RTU: A maximum of 4 Modbus participants can be connected to the Modbus terminal.
Modbus TCP: A maximum of 7 secondary meters can be used in the system.
IMPORTANT!
Only one primary meter, one battery and one Ohmpilot can be connected per inverter. Due to the high data transfer of the battery, the battery occupies 2 participants.
Example:
Input | Battery | Fronius | Number | Number |
---|---|---|---|---|
Modbus | 1 | 0 | ||
1 | 1 | |||
1 | 2 | |||
1 | 3 |
Grid | |
Inverter in the system | |
Utility meter | |
Primary meter | |
Secondary meter | |
Producer meter | |
Modbus RTU secondary device | |
Loads in the system | |
Additional loads in the system | |
Additional producers in the system | |
Terminating resistor |
If several Fronius Smart Meters are installed, a separate address must be set for each one (see Advanced settings on page (→)). The primary meter is always assigned address 1. All the other meters are numbered consecutively with the address range from 2 to 14. Different Fronius Smart Meter power categories can be used in combination.
IMPORTANT!
Max. 3 secondary meters may be used in the system. To avoid interference, it is recommended to install the terminating resistors according to chapter Terminating resistors on page (→).
IMPORTANT! Settings under the Device configuration menu item are only to be made by trained and qualified personnel!
The technician password must be entered in order to access the Device configuration menu item.
The Fronius Smart Meter IP can be operated in single-, two- and three-phase mode. In all cases, the selection is made under the Components menu area. The meter type is determined automatically.
A primary meter and several secondary meters can be selected. The primary meter needs to be configured first before a secondary meter can be selected.
The Fronius Smart Meter IP can be connected with Modbus TCP or Modbus RTU.
IMPORTANT! Settings under the Device configuration menu item are only to be made by trained and qualified personnel!
The technician password must be entered in order to access the Device configuration menu item.
The Fronius Smart Meter IP can be operated in single-, two- and three-phase mode. In all cases, the selection is made under the Components menu area. The meter type is determined automatically.
A primary meter and several secondary meters can be selected. The primary meter needs to be configured first before a secondary meter can be selected.
The Fronius Smart Meter IP can be connected with Modbus TCP or Modbus RTU.
WLAN:
The network wizard and the product setup can be carried out independently of each other. A network connection is required for the Fronius Solar.web installation wizard.
Ethernet:
The network wizard and the product setup can be carried out independently of each other. A network connection is required for the Fronius Solar.web installation wizard.
The Fronius Smart Meter IP is configured as the primary meter.
The Fronius Smart Meter IP is configured as a secondary meter.
Modbus RTU: The inputs M0 and M1 can be selected for this purpose. A maximum of 4 Modbus participants each can be connected to the Modbus terminal at inputs M0 and M1.
Modbus TCP: A maximum of 7 secondary meters can be used in the system.
IMPORTANT!
Only one primary meter, one battery and one Ohmpilot can be connected per inverter. Due to the high data transfer of the battery, the battery occupies 2 participants.
Example 1:
Input | Battery | Fronius | Number | Number |
---|---|---|---|---|
Modbus 0 | 0 | 4 | ||
0 | 2 | |||
0 | 1 | |||
Modbus 1 | 1 | 3 |
Example 2:
Input | Battery | Fronius | Number | Number |
---|---|---|---|---|
Modbus 0 | 1 | 3 | ||
Modbus 1 | 0 | 4 | ||
0 | 2 | |||
0 | 1 |
Grid | |
Inverter in the system | |
Utility meter | |
Primary meter | |
Secondary meter | |
Producer meter | |
Modbus RTU secondary device | |
Loads in the system | |
Additional loads in the system | |
Additional producers in the system | |
Terminating resistor |
If several Fronius Smart Meters are installed, a separate address must be set for each one (see Advanced settings on page (→)). The primary meter is always assigned address 1. All the other meters are numbered consecutively with the address range from 2 to 14. Different Fronius Smart Meter power categories can be used in combination.
IMPORTANT!
Max. 7 secondary meters may be used in the system. A data connection via RTU as well as TCP is possible. To avoid interference, it is recommended to install the terminating resistors according to chapter Setting the Modbus RTU terminating resistor on page (→).
| Measurement data and connections | |
| Language | |
| Change password Password guidelines
If the password has been forgotten, the Smart Meter must be reset (see chapter Restoring the factory settings on page (→). | |
| Advanced settings | |
| Info | |
| Logout |
| Measurement data and connections | |
| Language | |
| Change password Password guidelines
If the password has been forgotten, the Smart Meter must be reset (see chapter Restoring the factory settings on page (→). | |
| Advanced settings | |
| Info | |
| Logout |
| Measurement data and connections | |
| Language | |
| Change password Password guidelines
If the password has been forgotten, the Smart Meter must be reset (see chapter Restoring the factory settings on page (→). | |
| Advanced settings | |
| Info | |
| Logout |
Network The WLAN or LAN connection can be configured here. The use of a static IP address is recommended. | |
Meter values Here all values can be set to 0 or meter values can be corrected manually. The input current of the current transformers can be changed, see Changing the input current of the current transformers on page (→). | |
Software update Software update settings can be made here. It is possible to configure an automatic update. | |
Data interfaces Several data interfaces can be used simultaneously. Detailed views - Entering the login data is required.
| |
Single-phase/multiphase The connection type of the Fronius Smart Meter IP can be selected here. | |
Restart device Click on Restart device to restart the Fronius Smart Meter IP. |
Network The WLAN or LAN connection can be configured here. The use of a static IP address is recommended. | |
Meter values Here all values can be set to 0 or meter values can be corrected manually. The input current of the current transformers can be changed, see Changing the input current of the current transformers on page (→). | |
Software update Software update settings can be made here. It is possible to configure an automatic update. | |
Data interfaces Several data interfaces can be used simultaneously. Detailed views - Entering the login data is required.
| |
Single-phase/multiphase The connection type of the Fronius Smart Meter IP can be selected here. | |
Restart device Click on Restart device to restart the Fronius Smart Meter IP. |
Press and hold the WLAN access point and reset button for 20 seconds to reset the Fronius Smart Meter IP to factory settings.
Maintenance and servicing may only be carried out by Fronius-trained service technicians.
Maintenance and servicing may only be carried out by Fronius-trained service technicians.
Maintenance and servicing may only be carried out by Fronius-trained service technicians.
Clean the Fronius Smart Meter as required with a damp cloth.
Do not use cleaning agents, abrasives solvents or similar to clean the Smart Meter.
Waste electrical and electronic equipment must be collected separately and recycled in an environmentally responsible manner in accordance with the EU Directive and national law. Used equipment must be returned to the distributor or through a local, authorised collection and disposal system. Correct disposal of the used device promotes sustainable recycling of resources and prevents negative effects on health and the environment.
Packaging materialsDetailed, country-specific warranty conditions are available at www.fronius.com/solar/warranty.
To obtain the full warranty period for your newly installed Fronius product, please register at www.solarweb.com.
Measuring input | |
---|---|
Nominal voltage (3-phase) including tolerance | 208 - 480 V |
Nominal voltage (1-phase) including tolerance | 100 - 240 V |
Self-consumption | 30 mA |
Nominal frequency | 50 - 60 Hz |
Maximum current, Imax | 5000 A |
Short-time overload | 3x Imax / 20 s |
Self-consumption (max. current) | max. 5 W |
Current distortion factor | in acc. with EN IEC 62053-21 |
Power factor | active cosφ 0.5 ind - 0.8 cap, |
Current transformer (kCT) | 1 - 5000 Do not use Rogowski coils for measurement purposes! |
Energy | |
---|---|
Active energy accuracy | Class 1 |
Reactive energy accuracy | Class 2 |
Response time after switch-on | < 5 s |
Output | |
---|---|
RS485 communication | |
Standard | RS485 - 3 conductors |
Transmission | Serial, asynchronous |
Protocol | Modbus RTU |
Addresses | 1 - 255 |
Number of bits | 8 |
Stop bit | 1 |
Parity bit | None - even - odd |
Baud rate (Modbus transmission speed) | 9600 bit/s |
Response time | ≤ 200 ms |
WLAN | |
---|---|
Frequency range | 2412 - 2472 MHz |
Channels used | Channel: 1-13 b,g,n HT20 |
Output | <18 dBm |
Modulation | 802.11b: DSSS (1Mbps DBPSK, 2Mbps DQPSK, 5.5/11Mbps CCK) |
Insulation (EN IEC 62052-11, EN IEC 62053-21) | |
---|---|
Installation category | II |
Pollution degree | PD2 |
Insulation voltage | 4 kV RMS |
Impulse withstand voltage | 4 kV 1.2/60 µs |
Test voltage | 2.5 kV RMS. 50 Hz/1 min |
Test voltage | 4 kV RMS. 50 Hz/1 min |
Electromagnetic compatibility | |
---|---|
Test standard | Test in acc. with EN IEC 62052-11 |
Environmental conditions | |
---|---|
Reference temperature | 25 °C (± 5 °C) |
Operating range | -25 bis +55 °C |
Temperature limit for storage and transport | -30 to +80 °C |
Max. humidity | 93% |
Max. power loss (for thermal dimensioning of the switch cabinet) | ≤ 6 W |
Overvoltage category | III |
Housing | |
---|---|
Housing | 3 modules according to DIN 43880 |
Connection | Spring-loaded terminals |
Mounting | 35 mm DIN rail |
Housing material | PA-765 UL |
Protection class (EN 60529) | IP20 housing, IP30 connections |
Weight | 132 grams |
Terminals | |
---|---|
Voltage input | |
Wire | min. 1.5 mm² / max. 4 mm² |
Data output and current transformer input | |
Wire | min. 0.25 mm² / max. 2.5 mm² |
Measuring input | |
---|---|
Nominal voltage (3-phase) including tolerance | 208 - 480 V |
Nominal voltage (1-phase) including tolerance | 100 - 240 V |
Self-consumption | 30 mA |
Nominal frequency | 50 - 60 Hz |
Maximum current, Imax | 5000 A |
Short-time overload | 3x Imax / 20 s |
Self-consumption (max. current) | max. 5 W |
Current distortion factor | in acc. with EN IEC 62053-21 |
Power factor | active cosφ 0.5 ind - 0.8 cap, |
Current transformer (kCT) | 1 - 5000 Do not use Rogowski coils for measurement purposes! |
Energy | |
---|---|
Active energy accuracy | Class 1 |
Reactive energy accuracy | Class 2 |
Response time after switch-on | < 5 s |
Output | |
---|---|
RS485 communication | |
Standard | RS485 - 3 conductors |
Transmission | Serial, asynchronous |
Protocol | Modbus RTU |
Addresses | 1 - 255 |
Number of bits | 8 |
Stop bit | 1 |
Parity bit | None - even - odd |
Baud rate (Modbus transmission speed) | 9600 bit/s |
Response time | ≤ 200 ms |
WLAN | |
---|---|
Frequency range | 2412 - 2472 MHz |
Channels used | Channel: 1-13 b,g,n HT20 |
Output | <18 dBm |
Modulation | 802.11b: DSSS (1Mbps DBPSK, 2Mbps DQPSK, 5.5/11Mbps CCK) |
Insulation (EN IEC 62052-11, EN IEC 62053-21) | |
---|---|
Installation category | II |
Pollution degree | PD2 |
Insulation voltage | 4 kV RMS |
Impulse withstand voltage | 4 kV 1.2/60 µs |
Test voltage | 2.5 kV RMS. 50 Hz/1 min |
Test voltage | 4 kV RMS. 50 Hz/1 min |
Electromagnetic compatibility | |
---|---|
Test standard | Test in acc. with EN IEC 62052-11 |
Environmental conditions | |
---|---|
Reference temperature | 25 °C (± 5 °C) |
Operating range | -25 bis +55 °C |
Temperature limit for storage and transport | -30 to +80 °C |
Max. humidity | 93% |
Max. power loss (for thermal dimensioning of the switch cabinet) | ≤ 6 W |
Overvoltage category | III |
Housing | |
---|---|
Housing | 3 modules according to DIN 43880 |
Connection | Spring-loaded terminals |
Mounting | 35 mm DIN rail |
Housing material | PA-765 UL |
Protection class (EN 60529) | IP20 housing, IP30 connections |
Weight | 132 grams |
Terminals | |
---|---|
Voltage input | |
Wire | min. 1.5 mm² / max. 4 mm² |
Data output and current transformer input | |
Wire | min. 0.25 mm² / max. 2.5 mm² |