Indicates immediate danger.
If not avoided, death or serious injury will result.
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.
Indicates a risk of flawed results and possible damage to the equipment.
Indicates immediate danger.
If not avoided, death or serious injury will result.
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.
Indicates a risk of flawed results and possible damage to the equipment.
Indicates immediate danger.
If not avoided, death or serious injury will result.
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.
Indicates a risk of flawed results and possible damage to the equipment.
The Operating Instructions must always be at hand wherever the device is being used. In addition to the Operating Instructions, attention must also be paid to any generally applicable and local regulations regarding accident prevention and environmental protection.
All safety and danger notices on the device:The terminals can reach high temperatures.
Only operate the device when all protection devices are fully functional. If the protection devices are not fully functional, there is a danger of:Any safety devices that are not fully functional must be repaired by an authorised specialist before the device is switched on.
Never bypass or disable protection devices.
For the location of the safety and danger notices on the device, refer to the section headed "General remarks" in the Operating Instructions for the device.
Any equipment malfunctions which might impair safety must be remedied before the device is turned on.
This is for your personal safety!
Operation or storage of the device outside the stipulated area will be deemed as not in accordance with the intended purpose. The manufacturer accepts no liability for any damage resulting from improper use.
The servicing information contained in these operating instructions is intended only for the use of qualified service engineers. An electric shock can be fatal. Do not carry out any actions other than those described in the documentation. This also applies to qualified personnel.
All cables and leads must be secured, undamaged, insulated and adequately dimensioned. Loose connections, scorched, damaged or inadequately dimensioned cables and leads must be immediately repaired by authorised personnel.
Maintenance and repair work must only be carried out by an authorised specialist.
It is impossible to guarantee that bought-in parts are designed and manufactured to meet the demands made on them, or that they satisfy safety requirements. Use only original spare parts (also applies to standard parts).
Do not carry out any alterations, installations, or modifications to the device without first obtaining the manufacturer's permission.
Components that are not in perfect condition must be changed immediately.
In certain cases, even though a device complies with the standard limit values for emissions, it may affect the application area for which it was designed (e.g., when there is equipment that is susceptible to interference at the same location, or if the site where the device is installed is close to either radio or television receivers). If this is the case, then the operator is obliged to take action to rectify the situation.
Copyright of these operating instructions remains with the manufacturer.
Text and illustrations were accurate at the time of printing, subject to change.
We are grateful for suggestions for improvement and information regarding any discrepancies in the operating instructions.
The Fronius Backup Controller is a fixed piece of equipment designed for use in public grids with TN-C-S/TN-S systems. Its main function is to automatically and securely disconnect all connected loads and generators from the public grid in the event of a grid failure or grid malfunction in accordance with the specifications of the grid operator. As soon as grid stability has been restored, the loads and generators are automatically reconnected to the public grid.
The Fronius Backup Controller is a fixed piece of equipment designed for use in public grids with TN-C-S/TN-S systems. Its main function is to automatically and securely disconnect all connected loads and generators from the public grid in the event of a grid failure or grid malfunction in accordance with the specifications of the grid operator. As soon as grid stability has been restored, the loads and generators are automatically reconnected to the public grid.
Technical data and markings are located on the Fronius Backup Controller. These must NOT be removed or painted over.
Markings: | |
CE mark – confirms compliance with applicable EU directives and regulations. | |
WEEE mark – waste electrical and electronic equipment must be collected separately and recycled in an environmentally sound manner in accordance with the European Directive and national law. | |
RCM mark – tested in accordance with the requirements of Australia and New Zealand. |
(1) | Fronius Backup Controller |
(2) | Quick Start Guide |
(3) | Backup power warning notice |
PV module | |
Fronius GEN24 inverter | |
Fronius Backup Controller | |
Inverter in the system | |
Primary meter | |
Utility meter | |
Grid | |
Battery | |
Loads in the system |
The Fronius Backup Controller must be installed in the following position in the system.
Device name | Item number |
---|---|
Fronius Smart Meter IP | 42,0411,0347 |
Fronius Smart Meter 63A-3 | 43,0001,1473 |
Fronius Smart Meter TS 65A-3 | 43,0001,0044 |
(1) | 1-pin push-in terminal for the neutral conductor connection to the Fronius Smart Meter (max. 1 A). |
(2) | Push-in terminal for digital inputs/outputs. (I/Os). |
(3) | 3-pin push-in terminal for the supply from the public grid. |
(4) | 4-pin push-in terminal for the loads in the backup power circuit. |
(5) | 4-pin push-in terminal for the generators in the backup power circuit. |
(1) | 1-pin push-in terminal for the neutral conductor connection to the Fronius Smart Meter (max. 1 A). |
(2) | Push-in terminal for digital inputs/outputs. (I/Os). |
(3) | 3-pin push-in terminal for the supply from the public grid. |
(4) | 4-pin push-in terminal for the loads in the backup power circuit. |
(5) | 4-pin push-in terminal for the generators in the backup power circuit. |
I/O pin | Parameter | Description |
---|---|---|
IO 0 | Enable backup power locking | Before the inverter switches to backup power mode, the pin IO 0 must be active (value = 1). |
IN 6 | Grid relay open feedback | If the mains voltage is too low or the relay K3 is closed and therefore the relays K1, K2 and K4 are open, the auxiliary contacts of the mains isolation relays are closed and the pin IN 6 is active (value = 1). |
IN 7 | Locking feedback | When relay K3 is activated, the auxiliary contact of relay K3 closes and pin IN 7 is active (value = 1). The inverter receives feedback that relay K3 is closed. |
The LED status indicator shows the operating status and the Fronius Backup Controller.
Symbol | LED status | Description |
---|---|---|
Lights up green | The "Grid" LED indicates that all connected loads and generators in the backup power circuit are being supplied by or are connected to the public grid. | |
Lights steady blue | The "Full Backup" LED indicates that all connected loads and generators in the backup power circuit are safely disconnected from the public grid and that the Full Backup power supply is active. |
Single-core | Multi-stranded | Fine-stranded | Fine-stranded with ferrule and collar | Fine-stranded with ferrule without collar |
---|---|---|---|---|
Single-core | Multi-stranded | Fine-stranded | Fine-stranded with ferrule and collar | Fine-stranded with ferrule without collar |
---|---|---|---|---|
Single-core | Multi-stranded | Fine-stranded | Fine-stranded with ferrule and collar | Fine-stranded with ferrule without collar |
---|---|---|---|---|
Round copper conductors can be connected to the terminals as described below.
Push-in terminals for the supply from the public grid.* | ||||
---|---|---|---|---|
2.5 - 10 mm2 | 2.5 - 10 mm2 | 2.5 - 10 mm2 | 2.5 - 6 mm2 | 2.5 - 6 mm2 |
Push-in terminals for the loads/generators in the backup power circuit.* | ||||
---|---|---|---|---|
2.5 - 10 mm2 | 2.5 - 10 mm2 | 2.5 - 10 mm2 | 2.5 - 6 mm2 | 2.5 - 6 mm2 |
Push-in terminal for the neutral conductor connection to the Fronius Smart Meter (max. 1 A) | ||||
---|---|---|---|---|
1 - 4 mm2 | 1 - 4 mm2 | 1 - 4 mm2 | 1 - 2.5 mm2 | 1 - 2.5 mm2 |
Round copper conductors can be connected to the push-in terminals for digital inputs/outputs (I/Os) as described below.
IO connections with push-in terminal | ||||||
---|---|---|---|---|---|---|
Max. | Stripping length | Cable recommendation | ||||
30 m * | 10 mm | 0.14 - 1.5 mm2 | 0.14 - 1.5 mm2 | 0.14 - 1 mm2 | 0.14 - 1.5 mm2 | Single conductor possible |
* | Fronius recommends at least CAT 5 STP (shielded twisted pair) cables and a maximum distance of 30 m (32 yd). |
Danger from short circuits due to foreign bodies in the housing.
An electric shock can cause serious injury or death.
Cover vents during installation.
Danger due to incorrect operation and incorrectly performed work.
This can result in serious injury and damage to property.
Commissioning as well as maintenance and service work on the inverter and battery must only be carried out by service personnel trained by the respective inverter or battery manufacturer and only within the scope of the respective technical regulations.
Read the installation and operating instructions provided by the respective manufacturer before installing and commissioning the equipment.
Danger due to grid voltage and DC voltage from solar modules that are exposed to light and from batteries.
This can result in serious injury and damage to property.
Ensure that the AC and DC side of the inverter and the battery are de-energised before carrying out any connection, maintenance or service tasks.
Only an authorised electrical engineer is permitted to connect this equipment to the public grid.
Danger due to damaged and/or contaminated terminals.
This can result in serious injury and damage to property.
Before making any connections, check the terminals for damage and contamination.
Remove contamination in the de-energized state.
Have defective terminals repaired by an authorised specialist.
Danger from short circuits due to foreign bodies in the housing.
An electric shock can cause serious injury or death.
Cover vents during installation.
Danger due to incorrect operation and incorrectly performed work.
This can result in serious injury and damage to property.
Commissioning as well as maintenance and service work on the inverter and battery must only be carried out by service personnel trained by the respective inverter or battery manufacturer and only within the scope of the respective technical regulations.
Read the installation and operating instructions provided by the respective manufacturer before installing and commissioning the equipment.
Danger due to grid voltage and DC voltage from solar modules that are exposed to light and from batteries.
This can result in serious injury and damage to property.
Ensure that the AC and DC side of the inverter and the battery are de-energised before carrying out any connection, maintenance or service tasks.
Only an authorised electrical engineer is permitted to connect this equipment to the public grid.
Danger due to damaged and/or contaminated terminals.
This can result in serious injury and damage to property.
Before making any connections, check the terminals for damage and contamination.
Remove contamination in the de-energized state.
Have defective terminals repaired by an authorised specialist.
Turn off the automatic circuit breaker. Set the DC disconnector to the "Off" switch position.
Switch off the battery connected to the inverter.
Wait for the capacitors of the inverter to discharge (2 minutes).
The Fronius Backup Controller can be mounted on a 35 mm DIN rail. The housing comprises 8 modules according to DIN 43880 and conforms to unit size 2.
Danger due to individual conductors in the terminal that are loose and/or improperly connected.
This can result in serious injury and damage to property.
Only connect one single conductor in the slot provided for each terminal.
Check that the single conductor is held securely in the terminal.
Ensure that all of the single conductor is within the terminal and that no individual wires are sticking out of the terminal.
Strip the insulation of the single conductors by 12 mm.
Select the cable cross-section in accordance with the instructions in Permissible cables for the electrical connection from page (→).
Lift the operating levers of the terminals to open. Insert the stripped single conductors into the slot provided in the terminal, in each case as far as it will go.
Close the terminal operating levers until they engage.
Danger due to individual conductors in the terminal that are loose and/or improperly connected.
This can result in serious injury and damage to property.
Only connect one single conductor in the slot provided for each terminal.
Check that the single conductor is held securely in the terminal.
Ensure that all of the single conductor is within the terminal and that no individual wires are sticking out of the terminal.
Strip the insulation of the single conductors by 12 mm.
Select the cable cross-section in accordance with the instructions in Permissible cables for the electrical connection from page (→).
Lift the operating levers of the terminals to open. Insert the stripped single conductors into the slot provided in the terminal, in each case as far as it will go.
IMPORTANT!
The neutral conductor must be connected to the public grid.
Close the terminal operating levers until they engage.
Danger due to individual conductors in the terminal that are loose and/or improperly connected.
This can result in serious injury and damage to property.
Only connect one single conductor in the slot provided for each terminal.
Check that the single conductor is held securely in the terminal.
Ensure that all of the single conductor is within the terminal and that no individual wires are sticking out of the terminal.
Strip the insulation of the single conductors by 12 mm.
Select the cable cross-section in accordance with the instructions in Permissible cables for the electrical connection from page (→).
Lift the operating levers of the terminals to open. Insert the stripped single conductors into the slot provided in the terminal, in each case as far as it will go.
IMPORTANT!
The neutral conductor must be connected to the public grid.
Close the terminal operating levers until they engage.
Danger due to individual conductors in the terminal that are loose and/or improperly connected.
This can result in serious injury and damage to property.
Only connect one single conductor in the slot provided for each terminal.
Check that the single conductor is held securely in the terminal.
Ensure that all of the single conductor is within the terminal and that no individual wires are sticking out of the terminal.
Strip the insulation of the single conductors by 10 mm.
Select the cable cross-section in accordance with the instructions in Permissible cables for the electrical connection from page (→).
Lift the operating levers of the terminals to open. Insert the stripped single conductor into the slot provided in the terminal as far as it will go.
Close the operating lever of the terminal until it engages.
Switch on the battery connected to the inverter.
Set the DC disconnector to the "On" switch position. Switch on the automatic circuit breaker.
Switch on the battery connected to the inverter.
Set the DC disconnector to the "On" switch position. Switch on the automatic circuit breaker.
IMPORTANT!
Settings under the "Device configuration" → "Functions and I/Os" menu item are only to be made by trained and qualified personnel! The service password must be entered in order to access the "Device configuration" menu item.
The Full Backup backup power mode has been configured.
For test mode, a battery charge of min. 30% is recommended.
A description on how to run test mode can be found in the backup power checklist (https://www.fronius.com/en/search-page, item number: 42,0426,0365).
Clean the Backup Controller as required with a damp cloth.
Do not use cleaning agents, abrasives, solvents or similar to clean the Backup Controller.
Clean the Backup Controller as required with a damp cloth.
Do not use cleaning agents, abrasives, solvents or similar to clean the Backup Controller.
Maintenance and servicing may only be carried out by Fronius-trained service technicians.
Waste electrical and electronic equipment must be collected separately and recycled in an environmentally responsible manner in accordance with the EU Directive and national law. Used equipment must be returned to the distributor or through a local, authorised collection and disposal system. Correct disposal of the used device promotes sustainable recycling of resources and prevents negative effects on health and the environment.
Packaging materialsDetailed, country-specific warranty conditions are available at www.fronius.com/solar/warranty.
To obtain the full warranty period for your newly installed Fronius product, please register at www.solarweb.com.
General data | |
---|---|
Mains supply type | TN-S / TN-C-S |
Housing | 8 modules according to DIN 43880 |
Mounting | 35 mm DIN rail |
Weight | 625 g |
Protection class | IP 20 |
Fault Ride Through (FRT) | According to EN 50549-10 |
Short-circuit breaking capacity | Class PC |
Environmental conditions | |
---|---|
Permitted ambient temperature | -20 to +60 °C |
Permissible humidity | 50% relative humidity at 40 °C |
Max. altitude | 2000 m |
Vibrations | Not permitted |
Rated values | |
---|---|
Nominal voltage | 230 / 400 V 3-pole or 3-pole + N |
Nominal current | 35 A |
Duty cycle | 100% at AC-32 |
Rated power | 24 kVA |
Grid frequency | 50 Hz |
Power loss (at nominal current) | 15 W |
Overvoltage category | III |
Electromagnetic compatibility | |
---|---|
Immunity | According to EN 61000-6-2 2019-12-01 |
Emissions | According to EN 61000-6-3 2020-07 |