The warnings and safety instructions in these instructions are intended to protect people from possible injury and the product from damage.
Indicates an immediately dangerous situation
Serious injury or death will result if appropriate precautions are not taken.
Action step to escape the situation
Indicates a potentially dangerous situation
Death or serious injury may result if appropriate precautions are not taken.
Action step to escape the situation
Indicates a potentially dangerous situation
Minor or moderate injury may result if appropriate precautions are not taken.
Action step to escape the situation
Indicates impaired work results and/or damage to the device and components
The warnings and safety instructions are an integral part of these instructions and must always be observed to ensure the safe and proper use of the product.
The warnings and safety instructions in these instructions are intended to protect people from possible injury and the product from damage.
Indicates an immediately dangerous situation
Serious injury or death will result if appropriate precautions are not taken.
Action step to escape the situation
Indicates a potentially dangerous situation
Death or serious injury may result if appropriate precautions are not taken.
Action step to escape the situation
Indicates a potentially dangerous situation
Minor or moderate injury may result if appropriate precautions are not taken.
Action step to escape the situation
Indicates impaired work results and/or damage to the device and components
The warnings and safety instructions are an integral part of these instructions and must always be observed to ensure the safe and proper use of the product.
The warnings and safety instructions in these instructions are intended to protect people from possible injury and the product from damage.
Indicates an immediately dangerous situation
Serious injury or death will result if appropriate precautions are not taken.
Action step to escape the situation
Indicates a potentially dangerous situation
Death or serious injury may result if appropriate precautions are not taken.
Action step to escape the situation
Indicates a potentially dangerous situation
Minor or moderate injury may result if appropriate precautions are not taken.
Action step to escape the situation
Indicates impaired work results and/or damage to the device and components
The warnings and safety instructions are an integral part of these instructions and must always be observed to ensure the safe and proper use of the product.
The device has been manufactured in line with the state of the art and according to recognized safety standards.
Incorrect operation or misuse
Serious to fatal injuries to the operator or third parties as well as damage to the device and other property of the operator may result.
All persons involved in the commissioning, maintenance, and servicing of the device must be appropriately qualified and have knowledge of working with electrical installations.
Read these operating instructions in full and follow them carefully and precisely.
The operating instructions must always be kept to hand wherever the device is being used.
IMPORTANT!
In addition to the operating instructions, all applicable local rules and regulations regarding accident prevention and environmental protection must also be followed.
IMPORTANT!
Labels, warning notices, and safety symbols are located on the device. A description can be found in these operating instructions.
IMPORTANT!
All safety and danger notices on the device:Tampered-with and non-functioning protection devices
Serious to fatal injuries as well as damage to the device and other property of the operator may result.
Never bypass or disable protection devices.
Any protection devices that are not fully functional must be repaired by an authorized specialist before the device is switched on.
Loose, damaged, or under-dimensioned cables
An electric shock can be fatal.
Use undamaged, insulated, and adequately dimensioned cables.
Fasten the cables according to the specifications in the operating instructions.
Loose, damaged, or under-dimensioned cables must be repaired or replaced immediately by an authorized specialist.
Installations or modifications to the device
The device may be damaged
Do not carry out any alterations, installations, or modifications to the device without first obtaining the manufacturer's permission.
Damaged components must be replaced.
Only use original spare parts.
Operation or storage of the device outside the stipulated area will be deemed as not in accordance with the intended purpose.
The Fronius Smart Meter is a bidirectional electricity meter for optimizing self-consumption and recording a household's load characteristic curve. Together with a Fronius inverter or Fronius Datamanager 2.0 and a Fronius data interface, the Fronius Smart Meter allows you to view your own power consumption. The meter measures the energy flow to the loads or to the public grid and forwards the information to the Fronius inverter or Fronius Datamanager 2.0 via the Modbus RTU/RS485 interface.
Danger due to non-compliance with the safety instructions
Risk of injury and damage to the device as a result.
Follow all safety instructions.
Switch off the power supply before establishing the mains connection.
The Fronius Smart Meter is a bidirectional electricity meter for optimizing self-consumption and recording a household's load characteristic curve. Together with a Fronius inverter or Fronius Datamanager 2.0 and a Fronius data interface, the Fronius Smart Meter allows you to view your own power consumption. The meter measures the energy flow to the loads or to the public grid and forwards the information to the Fronius inverter or Fronius Datamanager 2.0 via the Modbus RTU/RS485 interface.
Danger due to non-compliance with the safety instructions
Risk of injury and damage to the device as a result.
Follow all safety instructions.
Switch off the power supply before establishing the mains connection.
Am Fronius Smart Meter befinden sich technische Daten, Kennzeichnungen und Sicherheitssymbole. Diese Informationen müssen in lesbarem Zustand gehalten werden und dürfen nicht entfernt, abgedeckt, überklebt oder übermalt werden. Die Hinweise und Symbole warnen vor Fehlbedienung, woraus schwerwiegende Personen- und Sachschäden resultieren können.
Symbole am Leistungsschild: | |
CE-Kennzeichnung | |
RCM (Regulatory Compliance Mark) | |
WEEE-Kennzeichnung |
The conventions regarding how information is presented in the document, which are set out below, have been defined in order to increase the readability and comprehensibility of the document.
Application notes
IMPORTANT! Indicates application notes and other useful information. It does not indicate a harmful or dangerous situation.
Software
Software functions and elements of a graphical user interface (e.g., buttons, menu items) are highlighted in the text with this mark up.
Example: Click Save.
Instructions for action
This document provides detailed information and instructions to ensure that all users can use the device safely and efficiently.
Data security for network and Internet connection
Unsecured networks and a lack of safeguards can result in data loss and unauthorized access. Observe the following points for safe operation:
Operate inverters and system components on a private, secure network.
Keep the network devices (e.g., WiFi routers) up to date with the latest technology.
Keep the software and/or firmware updated.
Use a wired network to ensure a stable data connection.
For security reasons, do not make inverters and system components accessible from the Internet via port forwarding or Port Address Translation (PAT).
Use the solutions provided by Fronius for monitoring and remote configuration.
The optional communication protocol Modbus TCP/IP1) is an unsecured interface. Only use Modbus TCP/IP if no other secured data communication protocol (MQTT2)) is possible (e.g., compatibility with older Smart Meters).
1) TCP/IP - Transmission Control Protocol/Internet Protocol
2) MQTT - Message Queuing Telemetry Protocol
Copyright of these operating instructions remains with the manufacturer.
Text and illustrations were accurate at the time of printing, subject to change.
We are grateful for suggestions for improvement and information on any discrepancies in the operating instructions.
The Fronius Smart Meter can be installed at two possible locations in the system, at the feed-in point and at the consumption point.
Positioning at the feed-in point
The positioning of the Fronius Smart Meter at the feed-in point.
Positioning at the consumption point
The positioning of the Fronius Smart Meter at the consumption point.
The Fronius Smart Meter can be installed at two possible locations in the system, at the feed-in point and at the consumption point.
Positioning at the feed-in point
The positioning of the Fronius Smart Meter at the feed-in point.
Positioning at the consumption point
The positioning of the Fronius Smart Meter at the consumption point.
The Fronius Smart Meter can be mounted on a 35 mm DIN rail. The housing comprises 4 DUs (division units, max. 72 mm).
The Fronius Smart Meter is a hard-wired device and requires a disconnecting device (circuit breaker, switch, or disconnector) and overcurrent protection (automatic circuit breaker).
The Fronius Smart Meter consumes 10 - 30 mA. The nominal capacity of the disconnecting devices and the overcurrent protection is determined by the wire thickness, the mains voltage, and the required breaking capacity.
Danger from mains voltage.
An electric shock can be fatal.
Switch off the power supply before connecting the mains voltage inputs to the Fronius Smart Meter.
IMPORTANT!
Do not install more than one cable per screw terminal. If necessary, use terminal blocks. The measuring inputs of the current transformers must be grounded on one side as shown in the circuit diagram.
Connect each voltage cable to the terminal strip as shown in the graphics below.
General
Do not use current transformers with a voltage output.
Current transformers are directional. If they are mounted backwards or with swapped wires, the measured power will be negative.
Primary current
Maximum current per phase. A current transformer with a primary current greater than the maximum expected current per phase should be selected. The closer the expected current is to this value, the more precise the measurement will be.
Secondary current
The current transformer must supply alternating current at a nominal current of 1 or 5 A. The nominal values for the current transformer are listed in the current transformer data sheet.
Power
The Fronius Smart Meter needs 0.3 VA to carry out its measurements. Losses also occur on the outgoing and return leads. The power of the current transformer must be greater than the sum total of the power of the Fronius Smart Meter and the leads. The higher the power, the better.
Line resistances at different cross-sections (copper wires) | ||||||
---|---|---|---|---|---|---|
Secondary current | Cross-section | Line resistances at different lead lengths (outgoing and return lead) | ||||
0.5 m | 1.0 m | 2.5 m | 5 m | 10 m | ||
5 | 1.5 | 0.3 VA | 0.6 VA | 1.5 VA | 2.9 VA | 5.8 VA |
5 | 2.5 | 0.2 VA | 0.4 VA | 0.9 VA | 1.8 VA | 3.6 VA |
5 | 4 | - | - | 0.6 VA | 1.1 VA | 2.2 VA |
Example
The length of the outgoing and return lead (0.5 m each) between the Fronius Smart Meter and the current transformer is a total of 1 m and has a copper cable cross-section of 1.5 mm²; the line resistance is therefore 0.6 VA according to the table above. The self-consumption of the Fronius Smart Meter is 0.3 VA.
Line resistance 0.6 VA + self-consumption 0.3 VA = 0.9 VA
→ A current transformer with a rating of 1 VA, 1.5 VA, 5 VA, or higher is suitable here.
Accuracy class
Use Class 1 or better (Class 0.5, 0.2, etc.). Class 1 is equivalent to a deviation of ± 1% of the secondary current at maximum power.
Mounting
Rigid or hinged.
"Rigid" is usually cheaper with better power and accuracy values. Hinged current transformers can be opened for attachment to the conductor. To prevent it being opened inadvertently, a plastic cable tie can be secured to the current transformer. Hinged current transformers can be installed in a system without interrupting the voltage.
Attach the current transformers to the conductor to be measured and connect the current transformer cables to the Fronius Smart Meter. Always switch off the power supply before disconnecting live conductors.
The current transformers are connected to connections 1 and 3; 4 and 6; 7 and 9. If necessary, excessively long cables can be shortened accordingly. Observe the sequence in which the phases are connected. Accurate power measurement is only ensured if the mains voltage phases match the current phases.
Suitable voltage transformers: Only voltage transformers with a voltage range from 210 to 440 V (phase - phase) may be used. The voltage transformers must be connected to terminals 2, 5, 8, and 11 at the point of direct voltage measurement.
Fronius SnapINverter:
Connect the data communication connections of the Fronius Smart Meter to the Fronius system monitoring in the inverter. Several Smart Meters can be installed in the system, see chapter Multi meter system - Fronius SnapINverter on page (→).
Fronius GEN24 inverter:
Connect the data communication connections of the Fronius Smart Meter to the Modbus interface of the Fronius GEN24 inverter. Several Smart Meters can be installed in the system, see chapter Multi meter system - Fronius GEN24 inverter on page (→).
More information on successful commissioning.
Note the following information about connecting the data communication cable to the inverter.
Use cables of type CAT5 or higher.
The maximum cable length between the Fronius inverter and Fronius Smart Meter is 300 meters.
Use a mutual twisted cable pair for data lines that belong together (D+, D- and M1+, M1-).
If the output cables are close to the grid cabling, use wires or cables that are designed for 300 V to 600 V (never less than the operating voltage).
Use double-insulated or sheathed output cables when they are close to bare conductors.
Use shielded twisted pair cables to avoid faults.
The outputs of the Fronius Smart Meter are electrically isolated from hazardous voltages.
Inverter in the system | |
Meter - Fronius Smart Meter | |
Fronius or third-party device, connection via Modbus RTU | |
Terminating resistor |
Due to interference, the use of terminating resistors according to the following overview is recommended for flawless operation.
* The terminating resistor on the Fronius Smart Meter is installed between 33 and 34. The terminating resistor R 120 Ohm is included with the Fronius Smart Meter.
Only the transformation ratio of the current and voltage transformers must be set. All other parameters have already been set in advance.
Password (0001):
Transformation ratio of the current transformers1) (0001 - 99992)):
Transformation ratio of the voltage transformers1), 3) (001.0 - 500.02)):
Change password and write it down4):
1) IMPORTANT! Changing the transformation ratios will reset the meter data in the Fronius Smart Meter to 0.
2) Transformation ratio in the current transformer x Transformation ratio of the voltage transformers = max. 1,000,000.
3) Changeover only when using voltage transformers (direct voltage measurement Vt = 1).
4) IMPORTANT! The password cannot be reset.
Grid | |
Inverter in the system | |
Utility meter | |
Primary meter | |
Secondary meter | |
Modbus RTU, Third-party device | |
Loads in the system | |
Additional loads in the system | |
Additional producers in the system | |
Terminating resistor |
A maximum of 4 Modbus stations can be connected to the Modbus connection terminal.
IMPORTANT!
Only one primary meter, one battery and one Ohmpilot can be connected per inverter. Due to the high data transfer of the battery, the battery occupies 2 subscribers.
Example:
Input | Battery | Fronius | Number | Number |
---|---|---|---|---|
Modbus | 1 | 0 | ||
1 | 1 | |||
1 | 2 | |||
1 | 3 |
If several Fronius Smart Meters are installed, a separate address must be set for each one (see Setting the address of the Fronius Smart Meter on page (→)). The primary meter always receives the address 1. All other meters are numbered consecutively in the address range from 2 to 14. Different Fronius Smart Meter power categories can be used together.
IMPORTANT!
Use no more than 3 secondary meters in the system. To avoid interference, it is recommended to install the terminating resistors according to the chapter Terminating resistors on page (→).
The inputs M0 and M1 can be freely selected. A maximum of 4 Modbus participants can be connected to the Modbus terminal on the inputs M0 and M1.
IMPORTANT!
Only one primary meter, one battery and one Ohmpilot can be connected per inverter. Due to the high data transfer of the battery, the battery occupies 2 subscribers.
Example 1:
Input | Battery | Fronius | Number | Number |
---|---|---|---|---|
Modbus 0 | 0 | 4 | ||
0 | 2 | |||
0 | 1 | |||
Modbus 1 | 1 | 3 |
Example 2:
Input | Battery | Fronius | Number | Number |
---|---|---|---|---|
Modbus 0 | 1 | 3 | ||
Modbus 1 | 0 | 4 | ||
0 | 2 | |||
0 | 1 |
If several Fronius Smart Meters are installed, a separate address must be set for each one (see Setting the address of the Fronius Smart Meter on page (→)). The primary meter always receives the address 1. All other meters are numbered consecutively in the address range from 2 to 14. Different Fronius Smart Meter power categories can be used together.
IMPORTANT!
Use no more than Use 7 secondary meters in the system. To avoid interference, it is recommended to install the terminating resistors according to the chapter Terminating resistors on page (→).
A graphic view of the menu structure can be found in the User Information that is supplied as standard.
Symbol | Name | Event | Function |
---|---|---|---|
Prog | 1 x | Increases the set value | |
Page | 1 x | Moves the cursor | |
Enter | 1 x | Confirms the entry |
Only configure the menu items "Password" and "Address".
The parameter „Node A“ is preset and must not be changed.
Symbol | Name | Event | Function |
---|---|---|---|
Page | 1 x | Continue to the next screen | |
Page | 5 seconds | Reset value / change menu |
The following illustrations are symbolic representations. The values displayed vary for each individual unit.
Display | Description |
---|---|
Total active energy consumed | |
Total reactive energy | |
Total active energy produced Press arrow key for 5 seconds to reset the value | |
Partial reactive energy Press arrow key for 5 seconds to reset the value | |
Maximum effective power average value Press arrow key for 5 seconds to reset the value | |
Effective power average value | |
Voltage and current menu Press the arrow key and wait 2 seconds until the next display (current phase L1) appears. | |
Current phase L1 | |
Current phase L2 | |
Current phase L3 | |
Chained voltage phase L1-L2 | |
Chained voltage phase L2-L3 | |
Chained voltage phase L1-L3 | |
Effective power | |
Reactive power | |
Apparent power |
IMPORTANT! Settings in the "Meter" menu item may only be entered by staff trained to do so!
The service password must be entered for the "Meter" menu item.
Three-phase or one-phase Fronius Smart Meters may be used. In both cases, selection is made via the "Fronius Smart Meter" item. The Fronius Datamanager automatically detects the meter type.
One primary meter and several secondary meters can be selected. The primary meter must be configured before a secondary meter can be chosen.
IMPORTANT! Settings in the "Meter" menu item may only be entered by staff trained to do so!
The service password must be entered for the "Meter" menu item.
Three-phase or one-phase Fronius Smart Meters may be used. In both cases, selection is made via the "Fronius Smart Meter" item. The Fronius Datamanager automatically detects the meter type.
One primary meter and several secondary meters can be selected. The primary meter must be configured before a secondary meter can be chosen.
IMPORTANT! Settings in the "Meter" menu item may only be entered by staff trained to do so!
The service password must be entered for the "Meter" menu item.
Three-phase or one-phase Fronius Smart Meters may be used. In both cases, selection is made via the "Fronius Smart Meter" item. The Fronius Datamanager automatically detects the meter type.
One primary meter and several secondary meters can be selected. The primary meter must be configured before a secondary meter can be chosen.
Access Point:
LAN:
The Fronius Smart Meter is configured as a primary meter.
The "Current general view" menu area displays the power of the PV modules, self-consumption, the energy fed into the grid, and the battery charge (if available).
The Fronius Smart Meter is configured as a secondary meter.
IMPORTANT! Settings in the "Device configuration" menu item may only be entered by staff trained to do so!
The service password must be entered for the "Device configuration" menu item.
Three-phase or one-phase Fronius Smart Meters may be used. In both cases, selection is made via the "Components" menu area. The meter type is determined automatically.
One primary meter and several secondary meters can be selected. The primary meter must be configured before a secondary meter can be chosen.
IMPORTANT! Settings in the "Device configuration" menu item may only be entered by staff trained to do so!
The service password must be entered for the "Device configuration" menu item.
Three-phase or one-phase Fronius Smart Meters may be used. In both cases, selection is made via the "Components" menu area. The meter type is determined automatically.
One primary meter and several secondary meters can be selected. The primary meter must be configured before a secondary meter can be chosen.
WLAN:
The network wizard and product setup can be performed independently. A network connection is required for the Fronius Solar.web installation wizard.
Ethernet:
The network wizard and product setup can be performed independently. A network connection is required for the Fronius Solar.web installation wizard.
The Fronius Smart Meter is configured as a primary meter.
The Fronius Smart Meter is configured as a secondary meter.
Modbus transmission speed: 9600 baud
Parity bit: None
Software version: Datamanager 3.7.2 / Energypackage 1.3.3
Input | |
---|---|
Three-phase nominal voltage | 400 - 415 V |
Single-phase nominal voltage | 230 - 240 V |
Voltage transformer ratio (kVT) | 1 - 1500.0 |
Self-consumption - voltage path (max. voltage) | 4.5 VA (1.85 W) for 440 V |
Nominal frequency | 50 - 60 Hz |
Nominal current, lb | 1 A + 5 A |
Maximum current, Imax | 6 A |
Starting current | 20 mA |
Current transformer ratio (kCT) | 1 - 9999 |
Short-time overload (EN/IEC 62053-21, EN/IEC 62053-23) | 20 lmax / 0.5 s |
Self-consumption - current path (max. current) | 0.3 W for phase |
Maximum value kVT x kCT | 5,000,000 (CT/1A) or 1,000,000 (CT/5A) |
Current total harmonic distortion | In acc. with EN/IEC 62053-21 |
Power factor | Active cosφ 0.5 ind to 0.8 cap, |
Energy | |
---|---|
Max. display | As per table |
Resolution | As per table |
LED indicator | 1 pulse / 0.1 Wh |
Active energy accuracy | Class 1 |
Reactive energy accuracy | Class 2 |
Response time after switch-on | < 5 s |
kCT x kVT | Maximum display |
| Resolution |
---|---|---|---|
1 to 9.9 | 9 9 9 9 9 9 . 9 9 | kWh / kvarh | 10 Wh / varh |
10 to 99.9 | 9 9 9 9 9 9 9 . 9 | kWh / kvarh | 100 Wh / varh |
100 to 999.9 | 9 9 9 9 9 9 9 9 | kWh / kvarh | 1 kWh / varh |
1000 to 9999.9 | 9 9 9 9 9 9 . 9 9 | MWh / kvarh | 10 kWh / varh |
≥ 10000 | 9 9 9 9 9 9 9 . 9 | MWh / kvarh | 100 kWh / varh |
Average power | |
---|---|
Measured variable | Effective power |
Calculation | Average value over set period of time |
Integration time | 5 / 8 / 10 / 15 / 20 / 30 / 60 minutes |
Operating hours counter | |
---|---|
Operating hours counter | Hours and minutes |
Resolution | 7-digit (5 hours + 2 minutes) |
Max. display | 99,999 h 59 min |
Counting start | 3-phase effective power |
Programmable values | 0.10 to 50% Pn |
3-phase effective power | In acc. with 400 V 5 A - 3464 W |
Operating hours counter reset | Accessible via keypad or locked |
Output | |
---|---|
Energy pulse | |
Contact load | 110 V DC/AC - 50 mA |
Assignable energy | Active or reactive energy |
Pulse value | 10 Wh (Varh) - 100 Wh (Varh) - 1 kWh (kVarh) - 10 kWh (kVarh) - 100 kWh (kVarh) - 1000 kWh (kVarh) |
Pulse duration | 50 - 100 - 150 - 200 - 300 - 400 - 500 ms |
RS485 communication | |
Standard | RS485 - 3 conductors |
Transmission | Serial, asynchronous |
Protocol | Modbus RTU |
Addresses | 1 to 255 |
Number of bits | 8 |
Stop bit | 1 |
Parity bit | None - even - odd |
Baud rate | 4800 - 9600 - 19200 bit/s |
Response time | ≤ 200 ms |
Insulation (EN/IEC 62052-11, 62053-21) | |
---|---|
Installation category | III |
Pollution degree | 2 |
Insulation voltage | 300 V phase-neutral |
Impulse withstand voltage | 5 kV 1.2/60 µs |
Test voltage | 2.75 kV r.m.s. 50 Hz / 1 min |
Test voltage | 4 kV r.m.s. 50 Hz / 1 min |
Electromagnetic compatibility | |
---|---|
Test in acc. with EN/IEC 62052-11 |
|
Operating conditions | |
---|---|
Reference temperature | 23 °C (±2 °C) |
Operating range | -5 to 55 °C |
Temperature limit for storage and transport | -25 to 70 °C |
Tropical model |
|
Max. power loss (for thermal dimensioning of the switch cabinet) | ≤ 2.8 W |
Housing | |
---|---|
Housing | 4 modules according to DIN 43880 |
Sealable front and terminal cover |
|
Connection | Screw connection |
Mounting | Can be snapped onto 35 mm DIN rail |
Housing material | Polycarbonate, self-extinguishing |
Degree of protection (EN 60529) | IP54 front, IP20 connections |
Weight | 260 grams |
Screw terminals | |
---|---|
Measuring input | |
Wire (rigid) | Min. 0.05 mm² / max. 4 mm² |
Wire (flexible) | Min. 0.05 mm² / max. 2.5 mm² |
Recommended torque | 0.5 Nm / max. 0.8 Nm |
Output | |
Wire (rigid) | Min. 0.05 mm² / max. 4 mm² |
Wire (flexible) | Min. 0.05 mm² / max. 2.5 mm² |
Recommended torque | 0.5 Nm / max. 0.8 Nm |
Modbus transmission speed: 9600 baud
Parity bit: None
Software version: Datamanager 3.7.2 / Energypackage 1.3.3
Input | |
---|---|
Three-phase nominal voltage | 400 - 415 V |
Single-phase nominal voltage | 230 - 240 V |
Voltage transformer ratio (kVT) | 1 - 1500.0 |
Self-consumption - voltage path (max. voltage) | 4.5 VA (1.85 W) for 440 V |
Nominal frequency | 50 - 60 Hz |
Nominal current, lb | 1 A + 5 A |
Maximum current, Imax | 6 A |
Starting current | 20 mA |
Current transformer ratio (kCT) | 1 - 9999 |
Short-time overload (EN/IEC 62053-21, EN/IEC 62053-23) | 20 lmax / 0.5 s |
Self-consumption - current path (max. current) | 0.3 W for phase |
Maximum value kVT x kCT | 5,000,000 (CT/1A) or 1,000,000 (CT/5A) |
Current total harmonic distortion | In acc. with EN/IEC 62053-21 |
Power factor | Active cosφ 0.5 ind to 0.8 cap, |
Energy | |
---|---|
Max. display | As per table |
Resolution | As per table |
LED indicator | 1 pulse / 0.1 Wh |
Active energy accuracy | Class 1 |
Reactive energy accuracy | Class 2 |
Response time after switch-on | < 5 s |
kCT x kVT | Maximum display |
| Resolution |
---|---|---|---|
1 to 9.9 | 9 9 9 9 9 9 . 9 9 | kWh / kvarh | 10 Wh / varh |
10 to 99.9 | 9 9 9 9 9 9 9 . 9 | kWh / kvarh | 100 Wh / varh |
100 to 999.9 | 9 9 9 9 9 9 9 9 | kWh / kvarh | 1 kWh / varh |
1000 to 9999.9 | 9 9 9 9 9 9 . 9 9 | MWh / kvarh | 10 kWh / varh |
≥ 10000 | 9 9 9 9 9 9 9 . 9 | MWh / kvarh | 100 kWh / varh |
Average power | |
---|---|
Measured variable | Effective power |
Calculation | Average value over set period of time |
Integration time | 5 / 8 / 10 / 15 / 20 / 30 / 60 minutes |
Operating hours counter | |
---|---|
Operating hours counter | Hours and minutes |
Resolution | 7-digit (5 hours + 2 minutes) |
Max. display | 99,999 h 59 min |
Counting start | 3-phase effective power |
Programmable values | 0.10 to 50% Pn |
3-phase effective power | In acc. with 400 V 5 A - 3464 W |
Operating hours counter reset | Accessible via keypad or locked |
Output | |
---|---|
Energy pulse | |
Contact load | 110 V DC/AC - 50 mA |
Assignable energy | Active or reactive energy |
Pulse value | 10 Wh (Varh) - 100 Wh (Varh) - 1 kWh (kVarh) - 10 kWh (kVarh) - 100 kWh (kVarh) - 1000 kWh (kVarh) |
Pulse duration | 50 - 100 - 150 - 200 - 300 - 400 - 500 ms |
RS485 communication | |
Standard | RS485 - 3 conductors |
Transmission | Serial, asynchronous |
Protocol | Modbus RTU |
Addresses | 1 to 255 |
Number of bits | 8 |
Stop bit | 1 |
Parity bit | None - even - odd |
Baud rate | 4800 - 9600 - 19200 bit/s |
Response time | ≤ 200 ms |
Insulation (EN/IEC 62052-11, 62053-21) | |
---|---|
Installation category | III |
Pollution degree | 2 |
Insulation voltage | 300 V phase-neutral |
Impulse withstand voltage | 5 kV 1.2/60 µs |
Test voltage | 2.75 kV r.m.s. 50 Hz / 1 min |
Test voltage | 4 kV r.m.s. 50 Hz / 1 min |
Electromagnetic compatibility | |
---|---|
Test in acc. with EN/IEC 62052-11 |
|
Operating conditions | |
---|---|
Reference temperature | 23 °C (±2 °C) |
Operating range | -5 to 55 °C |
Temperature limit for storage and transport | -25 to 70 °C |
Tropical model |
|
Max. power loss (for thermal dimensioning of the switch cabinet) | ≤ 2.8 W |
Housing | |
---|---|
Housing | 4 modules according to DIN 43880 |
Sealable front and terminal cover |
|
Connection | Screw connection |
Mounting | Can be snapped onto 35 mm DIN rail |
Housing material | Polycarbonate, self-extinguishing |
Degree of protection (EN 60529) | IP54 front, IP20 connections |
Weight | 260 grams |
Screw terminals | |
---|---|
Measuring input | |
Wire (rigid) | Min. 0.05 mm² / max. 4 mm² |
Wire (flexible) | Min. 0.05 mm² / max. 2.5 mm² |
Recommended torque | 0.5 Nm / max. 0.8 Nm |
Output | |
Wire (rigid) | Min. 0.05 mm² / max. 4 mm² |
Wire (flexible) | Min. 0.05 mm² / max. 2.5 mm² |
Recommended torque | 0.5 Nm / max. 0.8 Nm |
Detailed, country-specific warranty conditions are available at www.fronius.com/solar/warranty.
To obtain the full warranty period for your newly installed Fronius product, please register at www.solarweb.com.