Indicates an immediate danger.
Death or serious injury may result if appropriate precautions are not taken.
Indicates a possibly dangerous situation.
Death or serious injury may result if appropriate precautions are not taken.
Indicates a situation where damage or injury could occur.
Minor injury or damage to property may result if appropriate precautions are not taken.
Indicates the possibility of flawed results and damage to the equipment.
Indicates an immediate danger.
Death or serious injury may result if appropriate precautions are not taken.
Indicates a possibly dangerous situation.
Death or serious injury may result if appropriate precautions are not taken.
Indicates a situation where damage or injury could occur.
Minor injury or damage to property may result if appropriate precautions are not taken.
Indicates the possibility of flawed results and damage to the equipment.
The Operating Instructions must always be kept on hand wherever the device is being used. In addition to the Operating Instructions, all applicable local rules and regulations regarding accident prevention and environmental protection must also be followed.
All safety and danger notices on the deviceThe terminals can reach high temperatures.
Only operate the device when all protection devices are fully functional. If the protection devices are not fully functional, there is a risk ofAny safety devices that are not functioning properly must be repaired by an authorized specialist before the device is switched on.
Never bypass or disable protection devices.
For the location of the safety and danger notices on the device, refer to the section headed “General” in the Operating Instructions for the device.
Any equipment malfunctions which might impair safety must be remedied immediately before the device is turned on.
Your personal safety is at stake!
Operation or storage of the device outside the stipulated area will be deemed as not in accordance with the intended purpose. The manufacturer accepts no liability for any damage resulting from improper use.
The servicing information contained in these Operating Instructions is intended only for the use of qualified service engineers. An electric shock can be fatal. Do not carry out any actions other than those described in the documentation. This also applies to qualified personnel.
All cables and leads must be secured, undamaged, insulated, and adequately dimensioned. Loose connections, scorched, damaged, or under-dimensioned cables and leads must be repaired immediately by an authorized specialist.
Maintenance and repair work must only be carried out by an authorized specialist.
It is impossible to guarantee that externally (aka, third-party) procured parts are designed and manufactured to meet the demands made on them, or that they satisfy safety requirements. Use only original spare parts (also applies to standard parts).
Do not carry out any alterations, installations, or modifications to the device without first obtaining the manufacturer's permission.
Components that are not in perfect condition must be changed immediately.
Copyright of these operating instructions remains with the manufacturer.
Text and illustrations were accurate at the time of printing, subject to change.
We are grateful for suggestions for improvement and information on any discrepancies in the operating instructions.
The Fronius Smart Meter is a bidirectional electricity meter for optimizing self-consumption and recording a household's load characteristic curve. Together with a Fronius inverter or Fronius Datamanager 2.0 and a Fronius data interface, the Fronius Smart Meter allows you to view your own power consumption. The meter measures the energy flow to the loads or to the public grid and forwards the information to the Fronius inverter or Fronius Datamanager 2.0 via the Modbus RTU/RS485 interface.
Danger due to non-compliance with the safety instructions
Risk of injury and damage to the device as a result.
Follow all safety instructions.
Switch off the power supply before establishing the mains connection.
The Fronius Smart Meter is a bidirectional electricity meter for optimizing self-consumption and recording a household's load characteristic curve. Together with a Fronius inverter or Fronius Datamanager 2.0 and a Fronius data interface, the Fronius Smart Meter allows you to view your own power consumption. The meter measures the energy flow to the loads or to the public grid and forwards the information to the Fronius inverter or Fronius Datamanager 2.0 via the Modbus RTU/RS485 interface.
Danger due to non-compliance with the safety instructions
Risk of injury and damage to the device as a result.
Follow all safety instructions.
Switch off the power supply before establishing the mains connection.
Technical data, labels, and safety symbols are located on the Fronius Smart Meter. They must not be removed or painted over. They warn against incorrect operation, as this may result in serious injury and property damage.
Symbols on the rating plate: | |
CE label | |
RCM (Regulatory Compliance Mark) | |
WEEE label |
The Fronius Smart Meter can be installed at two possible locations in the system, at the feed-in point and at the consumption point.
Positioning at the feed-in point
The positioning of the Fronius Smart Meter at the feed-in point.
Positioning at the consumption point
The positioning of the Fronius Smart Meter at the consumption point.
The Fronius Smart Meter can be mounted on a 35 mm DIN rail. The housing comprises 4 DUs (division units, max. 72 mm).
The Fronius Smart Meter is a hard-wired device and requires a disconnecting device (circuit breaker, switch, or disconnector) and overcurrent protection (automatic circuit breaker).
The Fronius Smart Meter consumes 10 - 30 mA. The nominal capacity of the disconnecting devices and the overcurrent protection is determined by the wire thickness, the mains voltage, and the required breaking capacity.
Danger from mains voltage.
An electric shock can be fatal.
Switch off the power supply before connecting the mains voltage inputs to the Fronius Smart Meter.
IMPORTANT!
Do not install more than one cable per screw terminal. If necessary, use terminal blocks. Rate fuse according to the cross-section of the line.
Connect each voltage cable to the terminal strip as shown in the graphic below.
Fronius SnapINverter:
Connect the data communication connections of the Fronius Smart Meter to the Fronius system monitoring in the inverter. Several Smart Meters can be installed in the system, see chapter Multi meter system - Fronius SnapINverter on page (→).
Fronius GEN24 inverter:
Connect the data communication connections of the Fronius Smart Meter to the Modbus interface of the Fronius GEN24 inverter. Several Smart Meters can be installed in the system, see chapter Multi meter system - Fronius GEN24 inverter on page (→).
More information on successful commissioning.
Note the following information about connecting the data communication cable to the inverter.
Use cables of type CAT5 or higher.
The maximum cable length between the Fronius inverter and Fronius Smart Meter is 300 meters.
Use a mutual twisted cable pair for data lines that belong together (D+, D- and M1+, M1-).
If the output cables are close to the grid cabling, use wires or cables that are designed for 300 V to 600 V (never less than the operating voltage).
Use double-insulated or sheathed output cables when they are close to bare conductors.
Use shielded twisted pair cables to avoid faults.
The outputs of the Fronius Smart Meter are electrically isolated from hazardous voltages.
Inverter in the system | |
Meter - Fronius Smart Meter | |
Fronius or third-party device, connection via Modbus RTU | |
Terminating resistor |
Due to interference, the use of terminating resistors according to the following overview is recommended for flawless operation.
* The terminating resistor on the Fronius Smart Meter is installed between A and B. The terminating resistor R 120 Ohm is included with the Fronius Smart Meter.
Grid | |
Inverter in the system | |
Utility meter | |
Primary meter | |
Secondary meter | |
Modbus RTU, Third-party device | |
Loads in the system | |
Additional loads in the system | |
Additional producers in the system | |
Terminating resistor |
A maximum of 4 Modbus stations can be connected to the Modbus connection terminal.
IMPORTANT!
Only one primary meter, one battery and one Ohmpilot can be connected per inverter. Due to the high data transfer of the battery, the battery occupies 2 subscribers.
Example:
Input | Battery | Fronius | Number | Number |
---|---|---|---|---|
Modbus | 1 | 0 | ||
1 | 1 | |||
1 | 2 | |||
1 | 3 |
If several Fronius Smart Meters are installed, a separate address must be set for each one (see Setting the address of the Fronius Smart Meter on page (→)). The primary meter always receives the address 1. All other meters are numbered consecutively in the address range from 2 to 14. Different Fronius Smart Meter power categories can be used together.
IMPORTANT!
Use no more than 3 secondary meters in the system. To avoid interference, it is recommended to install the terminating resistors according to the chapter Terminating resistors on page (→).
The inputs M0 and M1 can be freely selected. A maximum of 4 Modbus participants can be connected to the Modbus terminal on the inputs M0 and M1.
IMPORTANT!
Only one primary meter, one battery and one Ohmpilot can be connected per inverter. Due to the high data transfer of the battery, the battery occupies 2 subscribers.
Example 1:
Input | Battery | Fronius | Number | Number |
---|---|---|---|---|
Modbus 0 | 0 | 4 | ||
0 | 2 | |||
0 | 1 | |||
Modbus 1 | 1 | 3 |
Example 2:
Input | Battery | Fronius | Number | Number |
---|---|---|---|---|
Modbus 0 | 1 | 3 | ||
Modbus 1 | 0 | 4 | ||
0 | 2 | |||
0 | 1 |
If several Fronius Smart Meters are installed, a separate address must be set for each one (see Setting the address of the Fronius Smart Meter on page (→)). The primary meter always receives the address 1. All other meters are numbered consecutively in the address range from 2 to 14. Different Fronius Smart Meter power categories can be used together.
IMPORTANT!
Use no more than Use 7 secondary meters in the system. To avoid interference, it is recommended to install the terminating resistors according to the chapter Terminating resistors on page (→).
A graphic view of the menu structure can be found in the User Information that is supplied as standard.
Symbol | Name | Event | Function |
---|---|---|---|
Prog | 1 x | Increases the set value | |
Page | 1 x | Moves the cursor | |
Enter | 1 x | Confirms the entry |
Symbol | Name | Event | Function |
---|---|---|---|
Page | 1 x | Continue to the next screen | |
Page | 2 seconds | Reset value / change menu |
The following illustrations are symbolic representations. The values displayed vary for each individual unit.
Display | Description |
---|---|
Total active energy consumed | |
Total reactive energy | |
Total active energy feed-in | |
Maximum effective power average value Press arrow key for 2 seconds to reset the value | |
Effective power average value | |
Voltage and current menu Press the arrow key and wait 2 seconds until the next display (current phase L1) appears. | |
Current phase L1 | |
Current phase L2 | |
Current phase L3 | |
Voltage phase L1 | |
Voltage phase L2 | |
Voltage phase L3 | |
Effective power | |
Reactive power | |
Apparent power | |
Effective power phase L1 | |
Effective power phase L2 | |
Effective power phase L3 | |
Reactive power phase L1 | |
Reactive power phase L2 | |
Reactive power phase L3 | |
Power factor phase L1 | |
Power factor phase L2 | |
Power factor phase L3 | |
Frequency / power factor |
IMPORTANT! Settings in the "Meter" menu item may only be entered by staff trained to do so!
The service password must be entered for the "Meter" menu item.
Three-phase or one-phase Fronius Smart Meters may be used. In both cases, selection is made via the "Fronius Smart Meter" item. The Fronius Datamanager automatically detects the meter type.
One primary meter and several secondary meters can be selected. The primary meter must be configured before a secondary meter can be chosen.
IMPORTANT! Settings in the "Meter" menu item may only be entered by staff trained to do so!
The service password must be entered for the "Meter" menu item.
Three-phase or one-phase Fronius Smart Meters may be used. In both cases, selection is made via the "Fronius Smart Meter" item. The Fronius Datamanager automatically detects the meter type.
One primary meter and several secondary meters can be selected. The primary meter must be configured before a secondary meter can be chosen.
IMPORTANT! Settings in the "Meter" menu item may only be entered by staff trained to do so!
The service password must be entered for the "Meter" menu item.
Three-phase or one-phase Fronius Smart Meters may be used. In both cases, selection is made via the "Fronius Smart Meter" item. The Fronius Datamanager automatically detects the meter type.
One primary meter and several secondary meters can be selected. The primary meter must be configured before a secondary meter can be chosen.
Access Point:
LAN:
The Fronius Smart Meter is configured as a primary meter.
The "Current general view" menu area displays the power of the PV modules, self-consumption, the energy fed into the grid, and the battery charge (if available).
The Fronius Smart Meter is configured as a secondary meter.
IMPORTANT! Settings in the "Device configuration" menu item may only be entered by staff trained to do so!
The service password must be entered for the "Device configuration" menu item.
Three-phase or one-phase Fronius Smart Meters may be used. In both cases, selection is made via the "Components" menu area. The meter type is determined automatically.
One primary meter and several secondary meters can be selected. The primary meter must be configured before a secondary meter can be chosen.
IMPORTANT! Settings in the "Device configuration" menu item may only be entered by staff trained to do so!
The service password must be entered for the "Device configuration" menu item.
Three-phase or one-phase Fronius Smart Meters may be used. In both cases, selection is made via the "Components" menu area. The meter type is determined automatically.
One primary meter and several secondary meters can be selected. The primary meter must be configured before a secondary meter can be chosen.
WLAN:
The network wizard and the product setup can be carried out independently of each other. A network connection is required for the Fronius Solar.web installation wizard.
Ethernet:
The network wizard and the product setup can be carried out independently of each other. A network connection is required for the Fronius Solar.web installation wizard.
The Fronius Smart Meter is configured as a primary meter.
The Fronius Smart Meter is configured as a secondary meter.
Modbus transmission speed: 9600 baud
Parity bit: none
Software version: Datamanager 3.7.2 / Energypackage 1.3.3
Input | |
---|---|
Nominal voltage (4-conductor) | 230 - 400 V |
Power consumption in the voltage path (max. voltage) | 2.2 VA (1.5 W) three-phase |
Nominal frequency | 50 - 60 Hz |
Nominal current, lb | 10 A |
Maximum current, Imax | 63 A |
Starting current | 40 mA |
Short-time overload (EN/IEC 62053-21, EN/IEC 62053-23) | 20 lmax / 0.5 s |
Self-consumption - current path (max. current) | 1.5 W for phase |
Power factor | Active cosφ 0.5 ind to 0.8 cap, |
Current total harmonic distortion | In acc. with EN 50470 |
Output | |
---|---|
RS485 communication | |
Standard | RS485 - 3 conductors |
Transmission | Serial, asynchronous |
Protocol | Compatible with Modbus RTU |
Addresses | 1 to 255 |
Number of bits | 8 |
Stop bit | 1 |
Parity bit | None - odd - even |
Baud rate | 4800 - 9600 - 19200 bit/s |
Response time | ≤ 200 ms |
Insulation (EN/IEC 62052-11, 62053-21) | |
---|---|
Installation category | III |
Degree of pollution | 2 |
Insulation voltage | 300 V phase-neutral |
Electromagnetic compatibility | |
---|---|
Emission test | In acc. with EN/IEC 62052-11, EN 50470 |
Immunity test | In acc. with EN/IEC 62052-11, EN 50470 |
Operating conditions | |
---|---|
Reference temperature | 23°C (±2°C) |
Operating range | -25 to 55 °C |
Temperature limit for storage and transport | -40 to 70 °C |
Tropical model |
|
Max. power loss (for thermal dimensioning of the switch cabinet) | ≤ 6 W |
Mechanical environment | M1 |
Housing | |
---|---|
Housing | 4 modules according to DIN 43880 |
Sealable front and terminal cover |
|
Connection | Screw connection |
Mounting | Can be snapped onto 35 mm DIN rail |
Housing material | Polycarbonate, self-extinguishing |
Degree of protection (EN 60529) | IP51 front, IP20 connections |
Weight | 260 grams |
Screw terminals | |
---|---|
Measuring input | |
Wire (rigid) | min. 1 mm² / max. 16 mm² |
Wire (flexible) | min. 1 mm² / max. 10 mm² |
Recommended torque | 1.2 Nm / max. 1.4 Nm |
Output | |
Wire (rigid) | min. 0.05 mm² / max. 4 mm² |
Wire (flexible) | min. 0.05 mm² / max. 2.5 mm² |
Recommended torque | 0.5 Nm / max. 0.8 Nm |
Modbus transmission speed: 9600 baud
Parity bit: none
Software version: Datamanager 3.7.2 / Energypackage 1.3.3
Input | |
---|---|
Nominal voltage (4-conductor) | 230 - 400 V |
Power consumption in the voltage path (max. voltage) | 2.2 VA (1.5 W) three-phase |
Nominal frequency | 50 - 60 Hz |
Nominal current, lb | 10 A |
Maximum current, Imax | 63 A |
Starting current | 40 mA |
Short-time overload (EN/IEC 62053-21, EN/IEC 62053-23) | 20 lmax / 0.5 s |
Self-consumption - current path (max. current) | 1.5 W for phase |
Power factor | Active cosφ 0.5 ind to 0.8 cap, |
Current total harmonic distortion | In acc. with EN 50470 |
Output | |
---|---|
RS485 communication | |
Standard | RS485 - 3 conductors |
Transmission | Serial, asynchronous |
Protocol | Compatible with Modbus RTU |
Addresses | 1 to 255 |
Number of bits | 8 |
Stop bit | 1 |
Parity bit | None - odd - even |
Baud rate | 4800 - 9600 - 19200 bit/s |
Response time | ≤ 200 ms |
Insulation (EN/IEC 62052-11, 62053-21) | |
---|---|
Installation category | III |
Degree of pollution | 2 |
Insulation voltage | 300 V phase-neutral |
Electromagnetic compatibility | |
---|---|
Emission test | In acc. with EN/IEC 62052-11, EN 50470 |
Immunity test | In acc. with EN/IEC 62052-11, EN 50470 |
Operating conditions | |
---|---|
Reference temperature | 23°C (±2°C) |
Operating range | -25 to 55 °C |
Temperature limit for storage and transport | -40 to 70 °C |
Tropical model |
|
Max. power loss (for thermal dimensioning of the switch cabinet) | ≤ 6 W |
Mechanical environment | M1 |
Housing | |
---|---|
Housing | 4 modules according to DIN 43880 |
Sealable front and terminal cover |
|
Connection | Screw connection |
Mounting | Can be snapped onto 35 mm DIN rail |
Housing material | Polycarbonate, self-extinguishing |
Degree of protection (EN 60529) | IP51 front, IP20 connections |
Weight | 260 grams |
Screw terminals | |
---|---|
Measuring input | |
Wire (rigid) | min. 1 mm² / max. 16 mm² |
Wire (flexible) | min. 1 mm² / max. 10 mm² |
Recommended torque | 1.2 Nm / max. 1.4 Nm |
Output | |
Wire (rigid) | min. 0.05 mm² / max. 4 mm² |
Wire (flexible) | min. 0.05 mm² / max. 2.5 mm² |
Recommended torque | 0.5 Nm / max. 0.8 Nm |
Detailed, country-specific warranty conditions are available at www.fronius.com/solar/warranty.
To obtain the full warranty period for your newly installed Fronius product, please register at www.solarweb.com.