Indicates an immediate danger.
Death or serious injury may result if appropriate precautions are not taken.
Indicates a possibly dangerous situation.
Death or serious injury may result if appropriate precautions are not taken.
Indicates a situation where damage or injury could occur.
Minor injury or damage to property may result if appropriate precautions are not taken.
Indicates the possibility of flawed results and damage to the equipment.
Indicates an immediate danger.
Death or serious injury may result if appropriate precautions are not taken.
Indicates a possibly dangerous situation.
Death or serious injury may result if appropriate precautions are not taken.
Indicates a situation where damage or injury could occur.
Minor injury or damage to property may result if appropriate precautions are not taken.
Indicates the possibility of flawed results and damage to the equipment.
Indicates an immediate danger.
Death or serious injury may result if appropriate precautions are not taken.
Indicates a possibly dangerous situation.
Death or serious injury may result if appropriate precautions are not taken.
Indicates a situation where damage or injury could occur.
Minor injury or damage to property may result if appropriate precautions are not taken.
Indicates the possibility of flawed results and damage to the equipment.
The Operating Instructions must always be kept on hand wherever the device is being used. In addition to the Operating Instructions, all applicable local rules and regulations regarding accident prevention and environmental protection must also be followed.
All safety and danger notices on the deviceThe terminals can reach high temperatures.
Only operate the device when all protection devices are fully functional. If the protection devices are not fully functional, there is a risk ofAny safety devices that are not functioning properly must be repaired by an authorized specialist before the device is switched on.
Never bypass or disable protection devices.
For the location of the safety and danger notices on the device, refer to the section headed “General” in the Operating Instructions for the device.
Any equipment malfunctions which might impair safety must be remedied immediately before the device is turned on.
Your personal safety is at stake!
Operation or storage of the device outside the stipulated area will be deemed as not in accordance with the intended purpose. The manufacturer accepts no liability for any damage resulting from improper use.
The servicing information contained in these Operating Instructions is intended only for the use of qualified service engineers. An electric shock can be fatal. Do not carry out any actions other than those described in the documentation. This also applies to qualified personnel.
All cables and leads must be secured, undamaged, insulated, and adequately dimensioned. Loose connections, scorched, damaged, or under-dimensioned cables and leads must be repaired immediately by an authorized specialist.
Maintenance and repair work must only be carried out by an authorized specialist.
It is impossible to guarantee that externally (aka, third-party) procured parts are designed and manufactured to meet the demands made on them, or that they satisfy safety requirements. Use only original spare parts (also applies to standard parts).
Do not carry out any alterations, installations, or modifications to the device without first obtaining the manufacturer's permission.
Components that are not in perfect condition must be changed immediately.
Copyright of these operating instructions remains with the manufacturer.
Text and illustrations were accurate at the time of printing, subject to change.
We are grateful for suggestions for improvement and information on any discrepancies in the operating instructions.
The Fronius Backup Switch is a piece of stationary equipment that was developed for use in public power grids with TN/TT systems. In the event of a grid failure, all connected loads and producers can be manually disconnected from the public grid in accordance with the specifications of the grid operator. The Fronius Backup Switch enables manual switching to the backup power supply. As soon as the public grid is stable again, the Fronius Backup Switch can be used to switch manually back to the power supply from the public grid. The Fronius Backup Switch can only be used in systems equipped with a battery storage system.
The Fronius Backup Switch is a piece of stationary equipment that was developed for use in public power grids with TN/TT systems. In the event of a grid failure, all connected loads and producers can be manually disconnected from the public grid in accordance with the specifications of the grid operator. The Fronius Backup Switch enables manual switching to the backup power supply. As soon as the public grid is stable again, the Fronius Backup Switch can be used to switch manually back to the power supply from the public grid. The Fronius Backup Switch can only be used in systems equipped with a battery storage system.
The Fronius Backup Switch is a piece of stationary equipment that was developed for use in public power grids with TN/TT systems. In the event of a grid failure, all connected loads and producers can be manually disconnected from the public grid in accordance with the specifications of the grid operator. The Fronius Backup Switch enables manual switching to the backup power supply. As soon as the public grid is stable again, the Fronius Backup Switch can be used to switch manually back to the power supply from the public grid. The Fronius Backup Switch can only be used in systems equipped with a battery storage system.
The Fronius Backup Switch is not suitable for the backup power supply of life-sustaining medical devices.
Technical data and markings are provided on the Fronius Backup Switch. They must not be removed or painted over.
Markings | |
CE label – confirms compliance with applicable EU directives and regulations. | |
C UL US LISTED marking – confirms compliance with applicable standards for Canada and the USA. |
IMPORTANT!
NO power categories of the US versions of the Fronius product series "Primo GEN24 X.X 208-240 (Plus) (SC)" are compatible with the Fronius Backup Switch.
(1) | 1 pc Fronius Backup Switch |
(2) | 2 pcs protective cover incl. 4 pcs screws B2.2 x 6.5 mm (not shown) |
(3) | 1 pc Quick Start Guide |
(4) | 1 pc "backup power supply" sticker |
PV module | |
Fronius GEN24 inverter | |
Fronius Backup Switch | |
Inverter in the system | |
Primary meter (Fronius Smart Meter) | |
Utility meter | |
Grid | |
Battery | |
Loads in the system |
The Fronius Backup Switch must be installed at the following position in the system.
IMPORTANT!
NO power categories of the US versions of the Fronius product series "Primo GEN24 X.X 208-240 (Plus) (SC)" are compatible with the Fronius Backup Switch.
Details on how to connect a Fronius Smart Meter can be found in the respective operating instructions.
To download the Smart Meter operating instructions, either click on the link Smart Meter operating instructions or visit the page fronius.com/en/solar-energy/installers-partners/downloads on an end device and enter the search term "Smart Meter".
The backup switch has three switch positions:
(1) | Grid operation The power is supplied by the public grid. |
(2) | 0-position (de-energized) The power supply is safely disconnected from the public grid or from the backup power supply. |
(3) | Backup power mode The power is supplied as backup power via the inverter or the battery. |
IMPORTANT!
In the switch position (2) the Backup Switch can be secured to prevent it from being switched on/off using a standard padlock. The national guidelines must be complied with in this respect.
The backup switch has three switch positions:
(1) | Grid operation The power is supplied by the public grid. |
(2) | 0-position (de-energized) The power supply is safely disconnected from the public grid or from the backup power supply. |
(3) | Backup power mode The power is supplied as backup power via the inverter or the battery. |
IMPORTANT!
In the switch position (2) the Backup Switch can be secured to prevent it from being switched on/off using a standard padlock. The national guidelines must be complied with in this respect.
(1) | Auxiliary contact switch terminals: Data communication |
(2) | Load disconnector 63 A terminals: Grid |
(3) | Load disconnector 20 A terminals: Data communication |
(4) | Auxiliary contact switch terminals: Data communication |
(5) | Load disconnector 63 A terminals: Load |
(6) | Load disconnector 20 A terminals: Data communication |
For information about installing data communication, see chapter Connecting the data communication cables on page (→).
Solid | Fine-stranded | Fine-stranded with ferrule and collar | Fine-stranded with ferrule without collar |
---|---|---|---|
Connect only round copper wires to the terminals. See tables below:
Terminals on load disconnector 63 A 1) | |||
---|---|---|---|
1 - 25 mm2 | 4 - 16 mm2 | 2.5 - 16 mm2 | 2.5 - 16 mm2 |
max. 2 x 10 mm2 | max. 2 x 10 mm2 |
Terminals on load disconnector 20 A 1) | |||
---|---|---|---|
0.13 - 10 mm2 | 0.5 - 6 mm2 | 0.5 - 6 mm2 | 0.5 - 6 mm2 |
Terminals on auxiliary contact switch | |||
---|---|---|---|
0.13 - 2.5 mm2 | 0.75 - 2.5 mm2 | 0.5 - 1.5 mm2 | 0.5 - 1.5 mm2 |
1) Select the cross-section of the sufficiently large cable. The cable cross-section depends on the power actually connected.
| Load disconnector 63 A | Load disconnector 20 A | Auxiliary contact switch |
---|---|---|---|
Connection screw | M5 | M3.5 | M3.5 |
Tightening torque | 2 - 4 Nm | 0.8 - 1.7 Nm | 0.8 - 1.4 Nm |
Conductors per terminal | 2 | 1 | 2 |
Danger due to short circuits resulting from foreign bodies in the connection area.
An electric shock can lead to serious injury or death.
Keep foreign objects away from the connection area or remove them if necessary.
Danger from incorrect operation and work that is not carried out properly.
This can result in severe personal injury and damage to property.
Only trained service technicians who have received training from the respective inverter or battery manufacturer are authorized to perform commissioning, maintenance, and service activities for inverters and batteries, and only within the scope of the technical regulations.
Read the installation instructions and operating instructions from the respective manufacturer before installing and commissioning the equipment.
Danger from mains voltage and DC voltage from PV modules that are exposed to light, as well as batteries.
This can result in severe personal injury and damage to property.
All connection, maintenance and service work should only be carried out when the AC and DC sides have been disconnected from the inverter and battery, and are de-energized.
Only an authorized electrical engineer is permitted to make the connection to the public grid.
Danger from damaged and/or contaminated terminals.
This can result in severe personal injury and damage to property.
Prior to connection work, check the terminals for damage and contamination.
Remove any contamination while the equipment is de-energized.
Have defective terminals repaired by an authorized specialist.
Danger due to short circuits resulting from foreign bodies in the connection area.
An electric shock can lead to serious injury or death.
Keep foreign objects away from the connection area or remove them if necessary.
Danger from incorrect operation and work that is not carried out properly.
This can result in severe personal injury and damage to property.
Only trained service technicians who have received training from the respective inverter or battery manufacturer are authorized to perform commissioning, maintenance, and service activities for inverters and batteries, and only within the scope of the technical regulations.
Read the installation instructions and operating instructions from the respective manufacturer before installing and commissioning the equipment.
Danger from mains voltage and DC voltage from PV modules that are exposed to light, as well as batteries.
This can result in severe personal injury and damage to property.
All connection, maintenance and service work should only be carried out when the AC and DC sides have been disconnected from the inverter and battery, and are de-energized.
Only an authorized electrical engineer is permitted to make the connection to the public grid.
Danger from damaged and/or contaminated terminals.
This can result in severe personal injury and damage to property.
Prior to connection work, check the terminals for damage and contamination.
Remove any contamination while the equipment is de-energized.
Have defective terminals repaired by an authorized specialist.
Turn off the automatic circuit breaker. Set the DC disconnector to the "off" (OFF) switch position.
Switch off the battery connected to the inverter.
Wait for the capacitors of the inverter to discharge (2 minutes).
The Fronius Backup Switch can be mounted on a 35 mm DIN rail.
Housing dimensions according to DIN 4388:
Before connecting the cables, the housing cover must be removed.
Load disconnector 63 A | Load disconnector 20 A | Auxiliary contact switch |
---|---|---|
14 mm (0.55 in.) | 11 mm (0.43 in.) | 8 mm (0.31 in.) |
Danger from loose and/or incorrectly clamped single conductors in the terminal.
This can result in severe personal injury and damage to property.
Check that the single conductors are secure in the terminal.
Make sure that the single conductor has been fully inserted into the terminal and that no single wires are protruding out of the terminal.
Plug the single conductor (L1 ) coming from the grid into the terminal.
Tighten the single conductor (L1 ) in the terminal. For permissible connection screws and torques, see Permitted connection screws on page (→).
Danger from loose and/or incorrectly clamped single conductors in the terminal.
This can result in severe personal injury and damage to property.
Check that the single conductors are secure in the terminal.
Make sure that the single conductor has been fully inserted into the terminal and that no single wires are protruding out of the terminal.
Plug the single conductor (L1 ) coming from the grid into the terminal.
Tighten the single conductor (L1 ) in the terminal. For permissible connection screws and torques, see Permitted connection screws on page (→).
Danger from loose and/or incorrectly clamped single conductors in the terminal.
This can result in severe personal injury and damage to property.
Check that the single conductors are secure in the terminal.
Make sure that the single conductor has been fully inserted into the terminal and that no single wires are protruding out of the terminal.
Plug the single conductor (L1‘) coming from the backup power circuit into the terminal.
Tighten the single conductor (L1‘) in the terminal. For permissible connection screws and torques, see Permitted connection screws on page (→).
Danger from loose and/or incorrectly clamped single conductors in the terminal.
This can result in severe personal injury and damage to property.
Check that the single conductors are secure in the terminal.
Make sure that the single conductor has been fully inserted into the terminal and that no single wires are protruding out of the terminal.
Plug the single conductors (L1 , L2 , L3 ) coming from the grid into the terminal.
Tighten the single conductors (L1 , L2 , L3 ) in the terminals. For permissible connection screws and torques, see Permitted connection screws on page (→).
Danger from loose and/or incorrectly clamped single conductors in the terminal.
This can result in severe personal injury and damage to property.
Check that the single conductors are secure in the terminal.
Make sure that the single conductor has been fully inserted into the terminal and that no single wires are protruding out of the terminal.
Plug the single conductors (L1 , L2 , L3 ) coming from the grid into the terminal.
Tighten the single conductors (L1 , L2 , L3 ) in the terminals. For permissible connection screws and torques, see Permitted connection screws on page (→).
Danger from loose and/or incorrectly clamped single conductors in the terminal.
This can result in severe personal injury and damage to property.
Check that the single conductors are secure in the terminal.
Make sure that the single conductor has been fully inserted into the terminal and that no single wires are protruding out of the terminal.
Plug the singles conductor (L1‘, L2‘, L3‘) coming from the backup power circuit into the terminals.
Tighten the single conductors (L1‘, L2‘, L3‘) in the terminals. For permissible connection screws and torques, see Permitted connection screws on page (→).
1) Wire the Fronius Smart Meter IP via Modbus so that the signal can be interrupted. The Fronius Smart Meter IP must not be connected to the network.
1) Wire the Fronius Smart Meter IP via Modbus so that the signal can be interrupted. The Fronius Smart Meter IP must not be connected to the network.
Feedback switch in backup power position (IN6/IN7)
When the Backup Switch is switched to backup power supply, the inverter checks the position of the switch. If this position is correct, the backup power supply of the connected loads in the backup power circuit is enabled.
Communication Modbus Smart Meter (M+/M-)
The communication between the inverter and the Fronius Smart Meter is interrupted via the contact. The interrupted communication prevents automatic termination of backup power mode. The inverter remains in backup power mode. If a stable power supply from the grid is available again, the switch of the Fronius Backup Switch must be switched to grid operation manually.
Wired Shut Down (WSD IN/WSD OUT)
In the "O" switch position, the WSD line is interrupted. The inverter switches off immediately. An asynchronous switchback to the grid is prevented.
Danger due to electrical voltage from missing or incorrectly fitted protective covers.
Electric shocks can be fatal and/or cause serious property damage.
Fit the protective covers immediately after installing the live cables
Fit the protective covers correctly and check that they are secure.
IMPORTANT!
The protective covers are used for additional insulation of the live lines to the data transfer lines.
Mount a top protective cover on the load disconnector 63 A. Fit using the screws supplied with the delivery.
Mount a bottom protective cover on the load disconnector 63 A. Fit using the screws supplied with the delivery.
Danger due to electrical voltage from missing or incorrectly fitted protective covers.
Electric shocks can be fatal and/or cause serious property damage.
Fit the protective covers immediately after installing the live cables
Fit the protective covers correctly and check that they are secure.
IMPORTANT!
The protective covers are used for additional insulation of the live lines to the data transfer lines.
Mount a top protective cover on the load disconnector 63 A. Fit using the screws supplied with the delivery.
Mount a bottom protective cover on the load disconnector 63 A. Fit using the screws supplied with the delivery.
Reinstall the housing cover and the switch and secure with the screw.
Reinstall the housing cover and the switch and secure with the screw.
Switch on the battery connected to the inverter.
Set the DC disconnector to the "on" switch position. Turn on the automatic circuit breaker.
Switch on the battery connected to the inverter.
Set the DC disconnector to the "on" switch position. Turn on the automatic circuit breaker.
IMPORTANT!
Settings in the "Device configuration" → "Functions and I/Os" menu item may only be implemented by staff trained to do so! The service password must be entered for the "Device configuration" menu item.
The Full Backup power mode has been configured.
For test mode, a battery charge of min. 30% is recommended.
A description on how to run test mode can be found in the backup power checklist (https://www.fronius.com/en/search-page, item number: 42,0426,0365).
Technical data 1) | Load disconnector | Load disconnector | Auxiliary contact switch | |
---|---|---|---|---|
Thermal rated operating current | ||||
open Ith | 63 A | 20 A | 10 A | |
encapsulated Ithe | 63 A | 20 A |
| |
Rated insulation voltage Ui 2) | 690 V | 690 V | 690 V | |
Breaking capacity Ieff |
|
|
| |
3 x 220 - 440 V | 330 A | 160 A |
| |
3 x 500 V | 330 A | 160 A |
| |
3 x 660 - 690 V | 190 A | 80 A |
| |
Utilization categories AC21A, AC21B |
|
|
| |
Rated operating current Ie | 400 V | 63 A | 20 A |
|
Rated operating power | 220 – 240 V | 24 kW | 8 kW |
|
380 – 440 V | 42 kW | 13 kW |
| |
3-phase 3-pin | 660 – 690 V | 72 kW | 23 kW |
|
Utilization categories AC23A, AC23B |
|
|
| |
Rated operating current Ie | 400 V | 45 A | 16 A |
|
Rated operating power | 220 – 240 V | 15 kW | 4 kW |
|
380 – 440 V | 22 kW | 7.5 kW |
| |
660 – 690 V | 18.5 kW | 5.5 kW |
| |
Fuse | gL (gG) | max. 63 A | max. 25 A | max. 20 A |
General data | |
---|---|
Weight | 421 g |
Permitted ambient temperature | -40 °C to +60 °C |
Dimensions | 64 x 125.4 x 91 mm |
Protection class | IP20 + KLAD |
Mains frequency | 50 - 60 Hz |
Nominal voltage | 3 - 230 / 400 V |
Grid disconnection | 1-pin or 3-pin |
1) According to IEC 947-3, IEC 947-5-1, VDE 0660, EN 60947-3, EN 60947-5-1
2) Applies to: Grids with grounded neutral point, overvoltage category I to III, pollution degree 3: Uimp = 6kV.
Technical data 1) | Load disconnector | Load disconnector | Auxiliary contact switch | |
---|---|---|---|---|
Thermal rated operating current | ||||
open Ith | 63 A | 20 A | 10 A | |
encapsulated Ithe | 63 A | 20 A |
| |
Rated insulation voltage Ui 2) | 690 V | 690 V | 690 V | |
Breaking capacity Ieff |
|
|
| |
3 x 220 - 440 V | 330 A | 160 A |
| |
3 x 500 V | 330 A | 160 A |
| |
3 x 660 - 690 V | 190 A | 80 A |
| |
Utilization categories AC21A, AC21B |
|
|
| |
Rated operating current Ie | 400 V | 63 A | 20 A |
|
Rated operating power | 220 – 240 V | 24 kW | 8 kW |
|
380 – 440 V | 42 kW | 13 kW |
| |
3-phase 3-pin | 660 – 690 V | 72 kW | 23 kW |
|
Utilization categories AC23A, AC23B |
|
|
| |
Rated operating current Ie | 400 V | 45 A | 16 A |
|
Rated operating power | 220 – 240 V | 15 kW | 4 kW |
|
380 – 440 V | 22 kW | 7.5 kW |
| |
660 – 690 V | 18.5 kW | 5.5 kW |
| |
Fuse | gL (gG) | max. 63 A | max. 25 A | max. 20 A |
General data | |
---|---|
Weight | 421 g |
Permitted ambient temperature | -40 °C to +60 °C |
Dimensions | 64 x 125.4 x 91 mm |
Protection class | IP20 + KLAD |
Mains frequency | 50 - 60 Hz |
Nominal voltage | 3 - 230 / 400 V |
Grid disconnection | 1-pin or 3-pin |
1) According to IEC 947-3, IEC 947-5-1, VDE 0660, EN 60947-3, EN 60947-5-1
2) Applies to: Grids with grounded neutral point, overvoltage category I to III, pollution degree 3: Uimp = 6kV.
Technical data 1) | Load disconnector | Load disconnector | Auxiliary contact switch | |
---|---|---|---|---|
Thermal rated operating current | ||||
open Ith | 63 A | 20 A | 10 A | |
encapsulated Ithe | 63 A | 20 A |
| |
Rated insulation voltage Ui 2) | 690 V | 690 V | 690 V | |
Breaking capacity Ieff |
|
|
| |
3 x 220 - 440 V | 330 A | 160 A |
| |
3 x 500 V | 330 A | 160 A |
| |
3 x 660 - 690 V | 190 A | 80 A |
| |
Utilization categories AC21A, AC21B |
|
|
| |
Rated operating current Ie | 400 V | 63 A | 20 A |
|
Rated operating power | 220 – 240 V | 24 kW | 8 kW |
|
380 – 440 V | 42 kW | 13 kW |
| |
3-phase 3-pin | 660 – 690 V | 72 kW | 23 kW |
|
Utilization categories AC23A, AC23B |
|
|
| |
Rated operating current Ie | 400 V | 45 A | 16 A |
|
Rated operating power | 220 – 240 V | 15 kW | 4 kW |
|
380 – 440 V | 22 kW | 7.5 kW |
| |
660 – 690 V | 18.5 kW | 5.5 kW |
| |
Fuse | gL (gG) | max. 63 A | max. 25 A | max. 20 A |
General data | |
---|---|
Weight | 421 g |
Permitted ambient temperature | -40 °C to +60 °C |
Dimensions | 64 x 125.4 x 91 mm |
Protection class | IP20 + KLAD |
Mains frequency | 50 - 60 Hz |
Nominal voltage | 3 - 230 / 400 V |
Grid disconnection | 1-pin or 3-pin |
1) According to IEC 947-3, IEC 947-5-1, VDE 0660, EN 60947-3, EN 60947-5-1
2) Applies to: Grids with grounded neutral point, overvoltage category I to III, pollution degree 3: Uimp = 6kV.
Maintenance and service work may only be carried out by Fronius-trained service technicians.
Maintenance and service work may only be carried out by Fronius-trained service technicians.
Waste electrical and electronic equipment must be collected separately and recycled in an environmentally sound manner in accordance with the European Directive and national law. Used equipment must be returned to the distributor or through a local authorized collection and disposal system. Proper disposal of the used device promotes sustainable recycling of resources and prevents negative effects on health and the environment.
Packaging materialsDetailed, country-specific warranty conditions are available at www.fronius.com/solar/warranty.
To obtain the full warranty period for your newly installed Fronius product, please register at www.solarweb.com.